Wiring Diagram - Panasonic S-20LM3HPQ Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20
W
IRING DIAGRAM
: FIELD WIRING
: TERMINAL
: CONNECTOR
,
: WIRE CLAMP
: PROTECTIVE EARTH (SCREW)
33H.........................FLOAT SWITCH
33S.........................LIMIT SWITCH (SWING FLAP)
A1P ........................PRINTED CIRCUIT BOARD
C1R ........................CAPACITOR (M1F)
F1T.........................THERMAL FUSE (125°C)(M1F EMBEDDED)
F1U ........................FUSE (250 V/5 A)
F2U ........................FIELD FUSE
HAP........................LIGHT EMITTING DIODE (SERVICE MONITOR - GREEN)
M1F ........................MOTOR (INDOOR FAN)
M1P........................MOTOR (DRAIN PUMP)
M1S........................MOTOR (SWING FLAP)
Q2E ........................EARTH LEAK DETECTOR
R1T ........................THERMISTOR (AIR)
R2T,R3T .................THERMISTOR (COIL)
RyA ........................MAGNETIC RELAY (M1S)
RyF1-3 ...................MAGNETIC RELAY (M1F)
RyP ........................MAGNETIC RELAY (M1P)
X1M........................TERMINAL STRIP (POWER)
X2M........................TERMINAL STRIP (CONTROL)
T1R ........................TRANSFORMER (220-240 V/22 V)
Y1E ........................ELECTRONIC EXPANSION CIRCUIT
RECEIVER/DISPLAY UNIT (ATTACHED TO WIRELESS REMOTE CONTROLLER)
A2P,A3P .................PRINTED CIRCUIT BOARD
BS ..........................ON/OFF BUTTON
H1P ........................LIGHT EMITTING DIODE (ON - RED)
H2P ........................LIGHT EMITTING DIODE (TIMER - GREEN)
H3P ........................LIGHT EMITTING DIODE (FILTER SIGN - RED)
H4P ........................LIGHT EMITTING DIODE (DEFROST - ORANGE)
SS1 ........................SELECTOR SWITCH (MAIN/SUB)
SS2 ........................SELECTOR SWITCH (WIRELESS ADDRESS SET)
CONNECTOR FOR OPTIONAL PARTS
X18A ......................CONNECTOR (ADAPTOR FOR ELECTRICAL APPENDICES)
X23A ......................CONNECTOR (WIRELESS REMOTE CONTROLLER)
RECEIVER/DISPLAY UNIT
WIRED REMOTE CONTROLLER
SWITCH BOX
TRANSMISSION WIRING
INPUT FROM OUTSIDE
CENTRAL REMOTE CONTROLLER
NOTE
1.
WHEN USING THE CENTRAL REMOTE CONTROLLER, SEE MANUAL FOR CONNECTION TO THE UNIT.
2.
X23A IS CONNECTED WHEN THE CENTRAL REMOTE CONTROLLER IS USED.
3.
WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE
SELECTED BY THE REMOTE CONTROLLER. SEE INSTALLATION MANUAL FOR MORE DETAILS.
Installation and operation manual
8
:
:
:
:
:
:
BLK
: BLACK
BLU
: BLUE
ORG
: ORANGE
PNK
: PINK
RED
: RED
WHT
: WHITE
YLW
: YELLOW
S-20~125LM3HPQ
Urban Multi air conditioner
4PW15112-1B

Publicité

Table des Matières
loading

Table des Matières