6. CONTROLS
6.1. 5 CONTROLS (OXYGEN CONTROL UNIT = OCU)
C1 = MAN
only manual operation using control panel
C2 = BMS
only 0 to 10 V analogue input (Building Management System)
C3 = BMSMAN
0 to 10 V analogue input plus manual control
C4 = CO2MAN
ventilation regulated based on CO2 plus manual control
C5 = SLAVE
the device that will be coupled to one of the above devices (cannot be indepen
dently installed) / the control is without a control panel.
For more information see info-fiche
6.2. CO
-CONTROL
2
The current generation of CO2 sensors has a built-in automatic calibration method.
In this case, the calibration is carried out by reaching the CO2 lower threshold of 400 ppm..
6.2.1. CO
-control / VOD1 - NL, ES, UK, D1
2
Q [m³/h]
Q max
Start
0%
900
950
increasing CO
6.2.2. CO
-control / VOD2 - BE, D2
2
Q [m³/h]
Q max
Q nom
40%
10%
650
increasing CO
82
1000 1050
1200
-values
2
850
950
-values
2
CO
[PPM]
2
decreasing CO
-values
2
CO
[PPM]
1300
2
decreasing CO
-values
2
1. valve opens
2. ventilator turns on
3. ventilator turns off
4. valve closes
1. Qnom is a calculated value
(according to NBN50-001)
and thus can vary.