Below is relevant error:
Debugging
——
code
LED1
progress
Display
Code
07_Detect indoor
db
components
XXXX is the project no. of the faulted IDU. 3s later, relevant error code is displayed. For
example, IDU no. 100 has d5 error, then LED3 displays like this: 01 (2s later) 00 (2s later) d5,
and repeat again.
Elimination methods of above error can be found in Troubleshooting.
Step 12: progress 08 is "Confirm preheated compressor"
If more than 8h of preheat time is detected, system will display as below and start next
progress.
——
Debugging code Progress code
LED1
progress
Display
Code
08_Confirm
preheated
db
compressor
If less than 8h of preheat time is detected, system will give error alarm and display as
below. Then press SW7 confirmation button to skip the wait time and start next progress. But
this will cause force start of the compressor, which may damage the compressor.
——
Debugging code Progress code
LED1
progress
Display
Code
08_Confirm
preheated
db
compressor
Step 13: progress 09 is "Refrigerant judgments before startup"
If the refrigerant quantity inside the system meets the requirement of operation startup,
system will display as below and start next progress.
——
Debugging code Progress code
LED1
progress
Display
Code
09_Refrigerant
judgments before
db
startup
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Progress code
LED2
Display
code
status
status
XXXXor
Light
07
Light
LED2
Display
code
status
status
Light
08
Light
LED2
Display
code
status
status
Light
08
Light
LED2
Display
code
status
status
Light
09
Light
Status code
LED3
Display
Code
status
System detects error in indoor
Error
Light
code
Status code
LED3
Display
Code
status
Preheat time for compressor is 8h. Start
OC
Light
Status code
LED3
Display
Code
status
Preheat time for compressor is less than
UO
Light
Status code
LED3
Display
Code
status
System refrigerant is normal. Start next
OC
Light
56
GMV DC Inverter VRF
Meaning
components.
Meaning
next progress.
Meaning
8h.
Meaning
progress.