Gree GMV-680WM/E-X Manuel D'utilisateur page 36

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

GMV DC Inverter VRF
(1) Pipeline charging amount
Pipeline charging amount A= ∑Liquid pipe length×refrigerant charging amount of every 1m
liquid pipe
Diameter of liquid
Φ28.6
pipe (mm)
kg/m
0.680
(2) ∑Refrigerant charging amount B of every module
Refrigerant charging amount B of every
module(kg)②
IDU/ODU rated capacity
collocation ratio C ①
50%≤C≤70%
70%<C≤90%
90%<C≤105%
105%<C≤135%
Note:
① IDU/ODU rated capacity collocation ratio C = Sum of rated cooling capacity of indoor
unit / Sum of rated cooling capacity of outdoor unit
② If all of the indoor units are fresh air indoor units, the quantity of refrigerant added to
each module is 0kg.
③ If outdoor air processor is connected with normal VRF indoor unit, adopt the perfusion
method for normal indoor unit for perfusion.
For example1:
Outdoor unit consists of one 28kW module and one 45kW module. Five 14kW duct type
units are used as indoor units.
IDU/ODU rated capacity collocation ratio C= 140×5/(280+450)=96%. The quantity of
included IDUs is more than 4 sets. Please refer to the above table.
Additional refrigerant quantity B for 28kW module is 2.0kg.
Additional refrigerant quantity B for 45kw module is 3.5kg.
So, ∑Refrigerant charging amount B of every module=2.0+3.5=5.5kg
Suppose the Pipeline charging amount A=∑Liquid pipe length×refrigerant charging amount
of every 1m liquid pipe=20kg
Total refrigerant charging amount R=20+5.5=25.5kg
For example 2:
Outdoor unit is a 45kW module and the indoor unit is a 45kW fresh air unit. The quantity (B)
of refrigerant added to this module is 0kg.
So, ∑B (Quantity of refrigerant added to each module) = 0kg
Suppose that A (Quantity of refrigerant added to connection pipe) = ∑Length of liquid pipe
x Quantity of refrigerant added to liquid pipe per meter) = 5kg
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Φ25.4
Φ22.2
Φ19.05
0.520
0.350
0.250
Quantity of
22.4
included IDUs
<4
0
≥4
0.5
<4
0.5
≥4
1.0
<4
1.0
≥4
2.0
<4
2.0
≥4
3.5
33
Φ15.9
Φ12.7
0.170
0.110
Module capacity(kW)
28.0
33.5
40.0
45.0 50.4
0
0
0
0
0.5
0.5
0.5
0.5
0.5
1.0
1.5
1.5
1.0
1.5
2.0
2.0
1.0
1.5
2.0
2.0
2.0
3.0
3.5
3.5
2.0
2.5
3.0
3.0
3.5
4.0
5.0
5.0
Φ9.52
Φ6.35
0.054
0.022
56.0
61.5
0
0
0
0.5
1.0
1.5
1.5
2.0
2.0
2.5
3.0
3.5
2.5
3.0
3.5
4.0
4.5
5
3.5
4.0
4.0
5.5
6.0
6.0