GMV DC Inverter VRF
Select the branch of outdoor module
Select the branch of outdoor module
4.2.5.3 Fitting pipe between two manifolds from basic modules
Pipe size (between two manifolds from basic modules) is based on the total capacity of
upstream modules.
Total capacity of upstream
modules Q(kW)
Q≤22.4
22.4<Q≤28.0
28.0<Q≤40.0
40.0<Q≤45.0
45.0<Q≤68.0
68.0<Q≤96.0
96.0<Q≤135.0
135.0<Q≤186.0
186.0<Q
4.2.5.4 Fitting pipe between the first manifold from indoor unit and the end manifold from
outdoor unit
Single module unit
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Model
ML01/A
Fig. 4.2.10
Pipe size between manifolds
Gas Pipe(mm)
Φ19.05
Φ22.2
Φ25.4
Φ28.6
Φ28.6
Φ31.8
Φ38.1
Φ41.3
Φ44.5
Fig. 4.2.11
23
Liquid Pipe(mm)
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Φ15.9
Φ19.05
Φ19.05
Φ19.05
Φ22.2