GMV DC Inverter VRF
Total rated capacity of outdoor modules
(multi-modular system)
GMV-1580WM/E-X
GMV-1630WM/E-X
GMV-1685WM/E-X
GMV-1750WM/E-X
GMV-1800WM/E-X
GMV-1845WM/E-X
GMV-1908WM/E-X
GMV-1962WM/E-X
GMV-2016WM/E-X
GMV-2072WM/E-X
GMV-2128WM/E-X
GMV-2184WM/E-X
GMV-2240WM/E-X
GMV-2295WM/E-X
GMV-2350WM/E-X
GMV-2405WM/E-X
GMV-2460WM/E-X
4.2.5.5 Manifold at indoor unit side
Manifold at indoor unit side can be selected as per total capacity of downstream indoor
unit(s). Refer to the following table.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Pipe between ODU and the first branch of IDU
Gas Pipe(mm)
Ф41.3
Ф41.3
Ф41.3
Ф41.3
Ф41.3
Ф41.3
Ф44.5
Ф44.5
Ф44.5
Ф44.5
Ф44.5
Ф44.5
Ф44.5
Ф44.5
Ф44.5
Ф44.5
Ф44.5
Fig. 4.2.13(a)
Fig. 4.2.13(b)
25
Liquid Pipe(mm)
Ф19.05
Ф19.05
Ф19.05
Ф19.05
Ф19.05
Ф19.05
Ф22.2
Ф22.2
Ф22.2
Ф22.2
Ф22.2
Ф22.2
Ф22.2
Ф22.2
Ф22.2
Ф22.2
Ф22.2