Powering On From The Mains; Powering Off The Cps - Gtec Saturn CPS 10 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

P
OWERING ON FROM THE
➢ Power the CPS by closing the SWIN input switch and leaving the SWMB maintenance switch open.
After a few moments, the CPS is turned on, the capacitors are precharged and the "Lock / stand-by" LED blinks: The
CPS is in stand-by mode.
➢ Press the
prompted to confirm, select "YES" and press the
All the LEDs around the display light up for about 1 sec. and a beep is emitted. The message "START UP" appears
on the display to inform the user of the beginning of the start up sequence which ends with transition of the CPS to
load powered by the inverter.
P
OWERING OFF THE
From the main menu, select "OFF" and press
submenu. Then select the option "YES – CONFIRM" and press
With the CPS in stand-by, in order to shut down the CPS completely, open the input disconnector SWIN and bypass
disconnector SWBYP.
Note: during prolonged periods of inactivity it is advisable to shut down the CPS by opening all disconnectors.
Lastly, with the CPS off, open the battery fuse holders.
M
AINS
CPS
- 88 -
button to access the power-on menu. When
button again.
to enter the
.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Saturn cps 15

Table des Matières