We recommend the INPUT/OUTPUT and BATTERY cables be passed under the CPS.
To determine the minimum cross section of the input and output cables, see the table below:
INPUT
mains / separate bypass
kVA
PE
L1/L2/L3
10
6
15
10
*
The cross sections indicated in the table refer to a maximum length of 10 metres
**
The maximum length of the cables for connecting the Battery Box (optional) is 3 metres
Note: the maximum cross section of the cables that may be inserted in the terminal board is:
▪ 10mm2 for cables with lugs
▪ 16mm2 for bare cables
C
ONNECTIONS
The first wire to be connected is the protective earth wire, which is to be inserted in the terminal
marked PE. During operation the CPS must be connected to the earthing system
Connect the input and output cables to the terminal board as indicated in the figure below:
THE INPUT AND BYPASS NEUTRALS MUST ALWAYS BE CONNECTED.
THE INPUT AND BYPASS LINES MUST REFER TO THE SAME NEUTRAL POTENTIAL.
Note: the connections to the BATTERY module are only to be made if the (optional) Battery Box is present.
C
ABLES
Cross section of cables (mm2)
N
PE
4
6
6
6
10
10
*
OUTPUT
L1/L2/L3
N
4
6
6
10
- 79 -
**
BATTERY
(optional)
PE
+/-
N
6
6
6
10
10
10