Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

CPS Models
Input stage
Rated voltage
Rated frequency
Accepted tolerance for input voltage without
activation of battery (for 400Vac)
Accepted tolerance for input frequency without
activation of battery (for 50/60Hz)
Cut-in threshold in Emergency Only mode and for
EOS
Cut-in time in Emergency Only mode
Input current harmonic distortion
Input power factor
Power Walk-in
Output stage
(1)
Rated voltage
(2)
Rated frequency
Rated apparent output power
Rated active output power
Output power factor
Short circuit current
Precision of output voltage (with respect to
output voltage 400Vac)
(3)
Static stability
Dynamic stability
Output voltage harmonic distortion with
standardized linear and distorting load
Crest factor allowed at rated load
Precision of frequency in free running mode
Inverter overload (Vin>345V AC )
Bypass Overload
Battery charger stage
Rated voltage
Maximum recharging current
Tolerance of input voltage for recharging at
maximum current

TECHNICAL DATA

(5)
CPS 10
380-400-415 Vac Three-phase with neutral (4 wires)
50-60Hz
20% @ 100% load
-40% +20% @50% load
20%
40-72Hz
- 20% of nominal voltage
< 300ms
THDi  3 %
≥0.99
Programmable from 1 to 125 sec. in steps of 1 sec.
380/400/415 Vac Three-phase with neutral (4 wires)
50/60Hz
10kVA
9kW
0,9
1,5x In for t>500ms
 1%
 0.5%
 3% resistive load
1% with linear load
3% with distorting load
3:1
0.01%
120% Infinite, 130% 10 min, 160% 1 min
130% Infinite,160% 60 minutes, 180% 10 minutes
240Vdc
6A
345-480Vac
- 113 -
CPS 15
(7)
15kVA
13.5kW
(4)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Saturn cps 15

Table des Matières