ALL THE OPERATIONS DESCRIBED IN THIS SECTION ARE TO BE PERFORMED EXCLUSIVELY BY
QUALIFIED STAFF.
The company declines all liability for damage caused by incorrect connections or operations not
described in this manual.
S
CPS
TORING THE
The storage room must respect the following conditions:
Temperature:
Relative humidity:
P
REPARING FOR INSTALLATION
P
I
RELIMINARY
NFORMATION
Modelli CPS
Rated power
Working temperature
Max. relative humidity during
operation
Max. height of installation
W x D x H
Weight
Power dissipated at rated resistive
load (pf=0.9) and with battery as
buffer *
Power dissipated at rated distortion
load (pf=0.7) and with battery charged
*
Flow rate of fans for removing heat
from installation room **
Current leak to earth ***
Isolation protection
Cable input
*
3.97 B.T.U./h = 1 kcal/h
** To calculate the air flow rate, the following formula may be used: Q [m3/h] = 3.1 x P diss [Kcal/h] / (t a - t e ) [°C]
P diss is the power expressed in Kcal/h dissipated by all the devices installed in the installation environment.
ta= ambient temperature, te=outside temperature. To take leaks into account, the value obtained should be increased
by 10%.
The table shows an example of a flow rate with (t a - t e )=5°C and a rated resistive load (pf=0.9).
(Note: This formula is applicable if ta>te, only; if not the CPS installation requires an air-conditioning system).
*** The leakage current of the load is to be added to that of the CPS on the earth wire.

INSTALLATION

B
AND THE
ATTERY
0°÷40°C (32°÷104°F)
max. 95%
w/o batteries
w/ batteries
B
OX
CPS 10
10000 VA
0 ÷ 40 °C
90 % (non-condensing)
1000 m at rated power
(-1% Power for every 100 m above 1000 m)
max 4000 m
440 x 850 x 1320 mm
110 Kg
320 Kg
0.63 kW
540 kcal/h
2150 B.T.U./h
0.49 kW
420 kcal/h
1670 B.T.U./h
340 mc/h
From bottom / on rear
- 69 -
CPS 15
15000 VA
120 Kg
0.86 kW
740 kcal/h
2940 B.T.U./h
0.67 kW
580 kcal/h
2290 B.T.U./h
460 mc/h
< 5 mA
IP20