Wire connection

REQUIREMENT
• Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Be sure to pass the wires through the bushing of wire connection holes of the indoor unit.
• Keep a margin (Approx. 100mm) on a wire to hang down the electrical control box at servicing, etc.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
1. Remove the cover of the electrical control box by taking off the mounting screws (2 positions)
2. Tighten the screws of the terminal block, and fix the wires with cord attached to the electrical control box.
(Do not apply tension to the connecting section of the terminal block.)
3. Mount the cover of the electrical control box without pinching wires.
<Terminal block of electrical control box>
Indoor fan power
supply Terminal
block
Bushing
Indoor fan power supply
wire
System interconnecting
wire
System
Wired remote controller
interconnecting
connecting Terminal
Terminal block
block
Wired remote
controller wire
Cord clamp
– 26 –
Installation Manual
Electrical
control box
cover
Fixing screw
EN
26-EN