Initial Setup

Instrument Setting
The instrument setting modifies the way the instrument
behaves, shown in the following table.
Setting A (Europe)
Line and Neutral Swap
allowed.
Auto Sequence RCD
does 5I test.
After RCD trip test,
contact voltage
displayed first.
2s
1
I no trip RCD test
2
not performed.
To change the setting:
1. Press and hold the Backlight key, then turn the
rotary selector switch from the OFF position to the
RCD 150mA 40ms position. The current setting will
be displayed.
2. To change the setting, toggle the I key until the
required setting is displayed.
3. To save the new setting, press the ENTER key. The
bleeper sounds and Std is displayed. To leave the
setting as it was, press the EXIT key.
6
Setting b (UK)
Line and neutral swap
not allowed.
Auto Sequence RCD
does 150mA test.
After RCD trip test,
trip time or current
displayed first.
2s
1
I no trip RCD test
2
performed.
Reset Factory Default Settings
The instrument will remember certain values such as
the VAR range RCD test current, even if the instrument
is switched off and the battery removed.
These can be reset to factory default settings as
follows:
1. Press and hold the Backlight key, then turn the
rotary selector switch from the OFF position to the
RCD 150mA 40ms position. The current setting will
be displayed. Release the backlight key.
2. Press the UP and DOWN keys together. The code
Clr is displayed.
3. Confirm the operation by pressing the ENTER key,
or abort by pressing any other key. The current
setting will be displayed.