nOTE The controller type must be set correctly before
making the wiring connection between the power
pack and the AquaLink
may be locked out of the AquaLink.
To verify the controller type is set correctly:
1.
Apply power to the power pack.
2.
Wait for the start-up sequence to complete.
3.
Press and hold the OUTPUT button for
approximately four (4) seconds. After four (4)
seconds, a controller type will be displayed on
the screen.
4.
Verify that the JANDY L/M controller type
appears on the display. If the contoller type
is not set to JANDY L/M, keep the OUTPUT
button pressed to toggle through the list of
contollers. Each controller will be displayed
on the screen for two (2) seconds. Release the
OUTPUT button when JANDY L/M appears on
the display.
3.7.2
Wiring to the Aqualink Rs Control
system or PDA
1.
Ensure that all power to the power pack and
the controller is disconnected/turned off at the
circuit breaker.
2.
Remove the screws attaching the cover to the
back plate and prop the cover up to expose the
terminals (see Figure 24).
nOTE Be carefully not to pull the ribbon cable that is
connected to the Power Supply and the Cover.
3.
Remove the white cap covering the comms hole
(see Figure 24).
4.
Thread the controller cable through the hole. A
grommet may be necessary depending on the
size of the cable being used.
5.
Attach a cable tie to the controller cable as
shown (see Figure 24).
Zodiac
AquaPure
®
, otherwise the power pack
®
|
Ei Series APURE35PLGC
Installation and Operation Manual
®
Prop the cover
on the two posts
located on
the back plate
Comm Hole

Figure 24. Accessing and Wiring to the Power PCB

6.
The Jandy AquaLink™
power pack
communicate and can be wired up to 152.4 m
(500 ft) apart. Any outdoor rated four conductor
cable, minimum 0.33 mm
used. Locate the appropriate screw terminals
on the circuit board and wire the power pack
the AquaLink
(see Figure 25).
The screw terminals on the AquaLink RS or PDA are
nOTE
removable to aid in installation.
Red, 4-Pin
Terminal Bar
4 3 2 1
OPTIONAL
Power Center

Figure 25. Communication Wiring between Power

Pack and Aqualink Rs Control system
or PDA network
Cable Tie
RS or PDA and
use a four (4) wire connection to
(22 AWG), can be
2
RS or PDA red 4-pin terminal bar
Power Pack
GRN
YEL
BLK
RED
to