Warning! Risk of personal injury!
The existing directives for accident prevention must be adhered to.
Warning! Risk of fatal electrical shock!
Danger from electrical current must be eliminated. Local directives or gen-
eral directives [e.g. IEC, VDE etc.] and those of local power supply companies
must be adhered to.
7.1 Installation
To ensure immunity in industrial environments (EN 61000-6-2) the data and
control cables must be shielded cables and must be used with an EMC-
compliant cable gland (included with the module).
WARNING! Danger of electric shock!
The pump should be electrically isolated and secured against unauthorised
switch-on before beginning installation of the IF-Module.
Installation steps in accordance with Fig. 2:
• Remove the lid of the pump's terminal box
• Remove the cover (1)
• Install the IF-Module in the pump's terminal box (2)
• Push the connection plug in all the way (3)
• Remove the existing PG 9 screwed connections (4a)
• Install the accompanying metal EMC cable glands (4b)
• Strip and prepare the shield and the core wires (4c)
• Insert the cable (4d)
• Screw the cable gland into place (4e)
Electrical connection follows (see section below).