Technical data: 600 and 1000Nm models
Implantation
Materials
Sealing
Environment
Operating temperature
Operating altitude
Hygrometry
Pollution degree
Noise level
Weight

Mechanical data

Maximum torque
Operating time (90°)
Angular range
Duty cycle
Drive ISO5211
Manual control

Electrical data

Electric connection
Technology of motors
Voltages
1)
Overvoltage category
2)
Power
Maximum current
Torque limiter
Number of feedback switches
Limit switches maximum voltage
Limit switches maximum current
Anticondensation heaters
1) The actuator tolerates voltage fluctuation of the electrical grid up to ± 10 % of its nominal system operating voltage
2) The actuator tolerates temporary overvoltages of the electrical grid
32
VT600
 
Housing: Aluminium + EPOXY coating
Shafts and screws : Stainless steel
Both inside and outside (wet environments possible)
-20 °C to +70 °C (BBPR: -10 °C to +40 °C)  
maximum relative humidity 80 % for temperatures up to 31 °C decreasing
linearly to 50 % relative humidity at 40 °C
Applicable POLLUTION DEGREE of the intended environment is 2
600 Nm
42 s
Secured handwheel without clutching system
3 x ISO M20 and specific multipin connector
100 V to 240 V AC 50/60 Hz and 100 V to 300 V DC
24 V to 48 V AC 50/60 Hz and 24 V to 72 V DC
TRANSIENT OVERVOLTAGES up to the levels of
OVERVOLTAGE CATEGORY ll
(example : 24 V : 13 A | 110 V : 3 A | 230 V : 1.5 A)
4 to 250 V AC/DC (Overvoltage category II)
VT1000
 
Drive: Steel + Zn treatment
IP 68  
Altitude up to 2000 m
(in most cases).
63 db
25 kg  
90° (180°-270° on request)
50 %
Star 36 - F10/F12
Brushless  
300 W  
13 A
Electronic
2 (4 in option)
1 mA to 5 A max.
3 x 7 W  
DSBA3600 • Rév. 05/11/2020
EN
1000 Nm
65 s