VALPES VT+ Manuel D'installation page 33

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
Technical data: 1500 and 2400Nm models
Implantation
Materials
Sealing
Environment
Operating temperature
Operating altitude
Hygrometry
Pollution degree
Noise level
Weight
Mechanical data
Maximum torque
Operating time (90°)
Angular range
Duty cycle
Drive ISO5211
Manual control
Electrical data
Electric connection
Technology of motors
Voltages
1)
Overvoltage category
2)
Power
Maximum current
Torque limiter
Number of feedback switches
Limit switches maximum voltage
Limit switches maximum current
Anticondensation heaters
1) The actuator tolerates voltage fluctuation of the electrical grid up to ± 10 % of its nominal system operating voltage
2) The actuator tolerates temporary overvoltages of the electrical grid
DSBA3600 • Rév. 05/11/2020
VT1500
 
Housing: Aluminium + EPOXY coating
Shafts and screws : Stainless steel
Both inside and outside (wet environments possible)
-20°C to +70 °C (BBPR: -10 °C to +40 °C)  
maximum relative humidity 80 % for temperatures up to 31 °C decreasing
linearly to 50 % relative humidity at 40 °C
Applicable POLLUTION DEGREE of the intended environment is 2
1500 Nm
155 s
Secured handwheel without clutching system
3 x ISO M20 and specific multipin connector
100 V to 240 V AC 50/60 Hz and 100 V to 300 V DC
24 V to 48 V AC 50/60 Hz and 24 V to 72 V DC
TRANSIENT OVERVOLTAGES up to the levels of
OVERVOLTAGE CATEGORY ll
(example : 24 V : 13 A | 110 V : 3 A | 230 V : 1.5 A)
4 to 250 V AC/DC (Overvoltage category II)
VT2400
 
Drive: Steel + Zn treatment
IP 68  
Altitude up to 2000 m
(in most cases).
63 db
57 kg  
90° (180°-270° on request)
50 %
Star 46 - F12/F14/F16
Brushless  
300 W  
13 A
Electronic
2 (4 in option)
1 mA to 5 A max.
3 x 7 W  
2400 Nm
210 s
33

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vt600Vt1000Vt1500Vt2400

Table des Matières