TERMINAL BOARD CONNECTIONS
1-2
Power input 230Vac, 50Hz, single-phase; 1 = Phase; 2 = Neutral;
3-4
Output for auxiliary courtesy light 230 Vac;
5-6
Flashing light output 230 Vac 20 W max.
7-8
433,92 MHz built-in RX aerial input; 7 = Earth 8 = Signal;
9-10
2
radio channel output;
nd
11-12
24 Vac output for powering safety and/or other devices (photocells, relays for lighting, etc);
13-15
Pressure-sensitive edge input; 13 = Pressure-sensitive edge; 15 = Common.
If the resistive sensitive edge is not used, do not short circuit terminals 13 and 15. The
input is only excluded by means of dip 9;
Note: if the resistive sensitive edge is used, to install the electric resistance pro-
vided as shown in enclosed instruction.
14-15
Input for pressure-sensitive edge (mechanical edge) or other safety devices, e.g. photo-
cells (NC contact); 14 = pressure-sensitive edge; 15 = Common;
16-17
Stop push button NC (normally closed) contact. After a stoppage, the system always starts
again with an opening phase and only after receiving a command from the On button or
radio transmitter. 16 = Common; 17 = Stop;
16-18
Input for open/close push button (normally-open contact): for usage, see the functions of
dip switches 2-3; 16 = Common; 18 = Open/close;
19-20-21 Motor (1) output; 19 = Closing phase; 20 = Common; 21 = Opening phase;
22-23-24 Auxiliary motor (2) output; 22 = Closing phase; 23 = Common; 24 = Opening phase;
M5
PIN1
Input for STOP push button
PIN2
Input for OPEN/CLOSE push button
PIN3
Common GND
PIN4
Input for closing limit switch FCC
PIN5
Input for opening limit switch FCA
Note: if the card is fitted in replacement of an older model (K595M, K696M, K797M or K898M)
there is no M5 terminal block. In its place is a terminal block with 3 screw units that must be
wired as follows:
25-26
Close limit switch input (Normally Closed contact) FCC; 25= Common;
25-27
Open limit switch input (Normally Closed contact) FCA; 25= Common.
M9
Encoder quick connector
PIN COM
PIN +5V
PIN ENC
NEW K892M FUNCTIONS (software version 3.10)
Board power-up:
On power-up with DIP4 set to ON, the board checks whether the work time is memorised. If this is not
detected, led DL7 flashes quickly, to indicate that the stroke setup procedure needs to be performed.
In all other cases, the first manoeuvre performed by the board is opening, unless already positioned
against one of the limit switches. During this phase, the board does not accept O/C inversion (Open/
Close).
BLUE negative
BROWN positive
WHITE signal
K892M
13