• Technical characteristics
Case
Dimensions:
Connection:
IP index:
Weight:
Display
Type:
Measurements
Three-phase (3 or 4 wires), two-phase (2 wire) and single-phase networks
Voltage (TRMS)
Direct measurement:
Measurement via PT:
Display and resolution
Update period:
Current (TRMS)
Via CT with:
Minimum measuring current
Input consumption:
Display:
Permanent overload:
Intermittent overload:
Update period:
Maximum ratio CT x VT
Power
Totale
Update period:
Frequency
Update period:
Operating conditions
Operating temperature:
Storage temperature:
Relative humidity:
EMDX
Power Quality Analyzer
96 x 96 x 62
96 x 96 x 81 with optional modules
2.5 mm
for removable terminal blocks (voltage and
2
modules) and 4 mm
for fixed terminals (current)
2
Front IP54, terminals IP20
285 g
Backlighted LCD display
50 ÷ 690 V AC (phase/phase)
30 ÷ 400 V AC (phase/phase)
• Primary: fino a 300 kV
0 ÷ 300,0 kV
1,1 s
• Primary: up to 9 999 A
• Secondary: 1 or 5 A
5 mA
≤ 0,2 VA
0,005 A ÷ 10 kA (
/1 A)
x
o
0,005 A ÷ 50 kA (
/5 A)
x
1,2 In
20 In per 0,5 s
1,1 s
10.000.000 (x/1 A)
2.000.000 (x/5 A)
0 ÷ 9999 kW / kvar / kVA
0 ÷ 9999 MW / Mvar / MVA
1,1 s
47,0 ÷ 63,0 Hz
1,1 s
(-5 °C) ÷ (55 °C) [23 °F ÷ 131 °F]
(-25 °C) ÷ (70 °C) [-13 °F ÷ 158 °F]
Suitable for tropical climates
Network and
3
55

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Emdx3 premium4 120 53