Energy-Efficient Use Of The Heat Pump; Purpose Of The Heat Pump; Application; Operating Principle - Dimplex LA 9TU Instructions D'installation Et D'utilisation

Table des Matières

Publicité

1.4 Energy-efficient use of the heat
pump
By operating this heat pump, you are helping to protect the envi-
ronment. A prerequisite for energy-efficient operation is the cor-
rect design of the heat source system and heating system.
It is particularly important for the efficiency of a heat pump to
keep the temperature difference between heating water and heat
source as small as possible. For this reason, it is advisable to
design the heat source and heating system very carefully. A tem-
perature difference of approx. one Kelvin (one °C) increases
the power consumption by around 2.5 %. When designing the
heating system, it should be borne in mind that special consum-
ers such as e.g. domestic hot water preparation should also be
taken into consideration and dimensioned for low temperatures.
Underfloor heating systems (panel heating) are optimally
suited for heat pump use on account of the low flow temperatures
(30 °C to 40 °C).
It is important to ensure that the heat exchangers are not con-
taminated during operation because this increases the tempera-
ture difference, in turn reducing the COP.
Correct adjustment of the heat pump manager is also important
for energy-efficient use of the heat pump. Further information can
be found in the operating instructions of the heat pump manager.
www.dimplex.de
2
Purpose of the heat
pump

2.1 Application

The air-to-water heat pump is to be used exclusively for the heat-
ing of heating water. It can be used in new or already-existing
heating systems.
The heat pump is suitable for mono-energy and bivalent opera-
tion down to an external temperature of -25 °C.
Proper defrosting of the evaporator is guaranteed by maintaining
a heating water return temperature of more than 18 °C during
continuous operation.
The heat pump is not designed for the increased heat consump-
tion required when a building is being dried out. For this reason,
the additional heat consumption should be met using special de-
vices provided by the customer. If a building is to be dried out in
autumn or winter, we recommend installing an additional electric
heating element (available as an accessory).
NOTE
The device is not suitable for operation with a frequency converter.

2.2 Operating principle

Surrounding air is drawn in by the fan and fed through the evap-
orator (heat exchanger). The evaporator cools the air, i.e. it ex-
tracts heat from it. This extracted heat is then transferred to the
working medium (refrigerant) in the evaporator.
The heat is brought to a higher temperature level by increasing
its pressure with the aid of an electrically driven compressor. It is
then transferred to the heating water via the liquefier (heat ex-
changer).
Electrical energy is used to raise the temperature of the heat in
the environment to a higher level. As the energy extracted from
the air is transferred to the heating water, this type of device is
called an air-to-water heat pump.
The Air-to-water heat pump consists of the main components:
evaporator, ventilator and expansion valve, as well as the low-
noise compressor, the liquefier and the electrical control system.
At low ambient temperatures, humidity accumulates on the evap-
orator in the form of frost, reducing the transfer of heat. Uneven
accumulation during this process does not indicate a fault. The
evaporator is defrosted automatically by the heat pump as re-
quired. Steam may be emitted from the air outlet depending on
the atmospheric conditions.
452163.66.09 · FD 9312
LA 9TU - LA 12TU
EN-3

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

La 12tu

Table des Matières