WMBUS ANALOG PWR - Guide utilisateur / User guide version V2.0.0
320
1
FR
321
1
EN
322
1
323
1
324
4
325
4
Configuration of the channel A sensor
Configuration of the event behaviour of
channel A
Configuration of the channel B sensor
Configuration of the event behaviour of
channel A
High threshold value channel A
Value of the high threshold hysteresis of
channel A:
Hexadecimal
Default : 0x00
Bits 0 à 3 : Type
• 0 = none
• 1 = 0-10 V
• 2 = 4-20 mA
Bits 4 to 7: Identifier (free to use)
WARNING : if none of the channels (A et B) is
configured (value = None), the product will send the
configuration frame 0x10 periodically (period defined
by register 300)
Hexadecimal
Default 0x10
Bits 0 à 1 : Threshold triggering
• 0 = None
• 1 = Low only
• 2 = High only
• 3 = Low and High
Bits 2 to 3: Trigger by digital input
• 0 = Disabled
• 1 = Rising edge
• 2 = Falling edge
• 3 = Rising and falling edges
Bits 4 to 7: Duration of the waiting period
• 0 : Aucune
• 1 : 10 ms
• 2 : 20 ms
• 3 : 50 ms
• 4 : 100 ms
• 5 : 200 ms
• 6 : 500 ms
• 7 : 1 s
Hexadecimal
See details of register 320
Hexadecimal
See details of register 321
Decimal
Default: 0
For a 4-20mA sensor:
• Unit: x 10nA
• Min/Max values: 400,000 to 2,000,000:
E.g.: If S324=1,100,000, the high threshold will have
a value of 11,000,00X10=11,000,000nA i.e.11mA
For a 0-10V sensor:
• Unit: x 1µV
• Min/Max values: 0 to 10,000,000:
E.g.: If S324=9,000,000, the high threshold will have
a value of 9,000,000µV i.e. 9V
Decimal
Default : 0
For a 4-20mA sensor:
• Unit: x 10nA
• Min/Max values: 0 à 1 600 000
E.g.: if S325=100 000, the value of the high threshold
hysteresis will be 100000x10=1 000 000nA soit 1mA
Pour un capteur 0-10V :
• Unité : x 1µV
• Valeurs Min/Max : 0 à 10 000 000
• 8 : 2 s
• 9 : 5 s
• A : 10 s
• B : 20 s
• C : 40 s
• D : 60 s
• E : 5
minutes
Page