Technical Data - Riello RLS 160/M MX FS2 Manuel D'entretien

Table des Matières

Publicité

TECHNICAL DATA

MODEL
TYPE
OUTPUT
(1)
DELIVERY
(1)
light oil
natural gas
FUEL
Gas pressure at maximum delivery
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATUR
COMBUSTION AIR TEMPERATURE
PUMP
delivery (at 12 bar)
pressure range
fuel temperatur
CONFORMITY TO EEC DIRECTIVES
NOISE LEVELS
Sound pressure
(3)
Sound power
APPROVAL
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m s.l.m.
(2) Pressure at test point 4)(A)p.12 with zero pressure in the combustion chamber and maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output.
The sound power is evaluated, in line with the regulations, on a spherical surface centred on the burner and with a radius of 1 metre.
2nd stage
kW
(min - max)
kg/h
kW
1st stage (min)
kg/h
2nd stage
kW
(min - max)
1st stage (min)
kW
Gas: G20/G25
mbar
(2)
number
°C
°C max
kg/h
bar
° C max
dBA
CE
Flame stability disk with circular
sectors 3)(D)p. 16
965 - 1846
81 - 155
488
41
940 - 1730
300
Light oil, viscosity at 20 °C: 6 mm
Natural gas: G20 (methane) - G21 - G22 - G23 - G25
- Continuous
- Light oil: Two-stage (high and low flame) and single-stage (all - nothing)
- Gas: Progressive two-stage or modulating by kit (see ACCESSOIRES)
Boilers: water, steam, diathermic oil
2009/142 - 2006/95 - 2004/108
7
RLS 160/M MX
781 T
Flame stability disk without circular
sectors 3)(D)p. 16
1132 - 2013
95 - 169
560
47
940 - 1840
300
2
/s max (1,5 °E - 6 cSt)
14 / 21
2
0 - 40
60
230
10 - 21
90
80.5
91.5
0085BN0625

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

781 t389822038982212001164420011645

Table des Matières