Location of chimney terminals

Dimension Terminal Position
A*
Directly under an opening, an open window or ventilation duct
B
Above an opening, an open window or ventilation duct
C
Alongside an opening, opening window etc.
D
Under gutter, earth pipes or drainpipes
E
Under eaves
F
Under balconies or carport roof
G
From a vertical drainpipe or earth pipe
H
From an internal or external corner
I
Overground roof or balcony level
J
From a surface facing the terminal
K
From a terminal facing the terminal
L
From an opening in carport (e.g., door, window into the dwelling)
M
Vertical from a terminal on same wall
N
Vertical from a terminal on same wall
P
From a vertical construction on the roof
Q
Above the intersection with roof
* In addition, the terminal must not be closer than 300 mm to an opening in the building, such as a
28
window or a door.
attika
RAIS/
- User manual for Q-Tee II Gas / Q-Tee II C Gas
Distance (mm)
600
300
400
300
300
600
300
600
300
600
600
1200
1500
300
600
300