4.3 Starting compactSteam

Before starting the unit, verify that the power supply voltage is
correct, and the characteristics of the circuit breaker installed.
For CH004N0003 units, make sure that the procedure in paragraph
3.7 for setting the correct supply voltage has been completed.
Press the ON button (13), the unit switches on and the display
shows 03, with the 'SET' symbol flashing. To complete the guided
configuration procedure, press the 'RESET/SEL' button and then
adjust the value shown on the display.
Choose the desired value from the four options shown below and
press the 'DRAIN/ENT' button to confirm.
1 115V 11A 1.6 kg/h (model CH004N0003 only)
2  115V 14.5A 2.2 kg/h (model CH004N0003 only)
3  230V 11A 3.3 kg/h (all models)
4  230V 14,5A 4.5 kg/h (all models)
At the end of this initialization operation, a sequence of characters
will be shown on the display to indicate the selected size and
voltage, according to the following scheme:
CH + size (kg/h) + U + voltage (1 = 115V, 2 = 230V)
CH01U1 : 1.6 kg/h 115V (model CH004N0003 only)
CH02U1: 2.2 kg/h 115V(model CH004N0003 only)
CH03U2: 3.3 kg/h 230V (all models)
CH04U2: 4.5 kg/h 230V (all models)
If, on the other hand, no selection is made within 10 seconds, the
unit will start using the default setting (option 3). The unit can be
configured again the next time it is switched on.
The yellow power LED comes on and compactSteam is ready to
operate.
If humidity production is required, compactSteam powers on the
boiler electrodes and the green operating LED comes on. Even
if not configured, the unit is enabled for production, but the
warning EH will be shown on the display.
4.4 Cylinder pre-wash (first start-up or
replacement)
1. Switch the unit off if it already on.
Press and hold the 'SEL' and 'DRAIN' buttons together
and then switch the unit on using the ON/OFF button,
while still keeping the two buttons pressed until the
spanner symbol starts flashing, then release the buttons.
2. Press 'SEL' until the value 04 is shown on the display.
Warning: DO NOT confirm any value greater than 04. If a number
greater than or equal to 05 is displayed, press 'SEL' until the counter
restarts from 0 again and continue until reaching the value 04.
3.
Press 'DRAIN' (at least 1 second). The cleaning cycle starts.
In this phase, the electrodes are powered on and the cylinder is
filled with water, until one of the following conditions occurs:
- the water level reaches the maximum fill sensor;
- the phase current is equal to the nominal value.
The cylinder is emptied. Carel recommends carrying out two
cleaning cycles. (Go back and repeat from point 1).