G
®
HYGRASREG
RHT - 30
Electronic room hygrostat and/or room thermostat HYGRASREG
thresholds, with ⁄ without optional display for indicating ACTUAL humidity and/or ACTUAL temperature (accuracy class ± 3 % r.H.). The setpoints can
be allocated to the relative humidity and/or to the temperature. It is suitable for regulating and monitoring relative humidity (humidifying and
dehumidifying) and/or the temperature (heating and cooling), e.g. in ventilation and air conditioning ducts, laboratories, production facilities, climatic
test cabinets, indoor swimming pools, greenhouses, etc., to control humidifying and dehumidifying equipment or heating system control. The measuring
transducers are designed for exact humidity/temperature measurement. The RHT-30 uses a digital, long-term stable sensor as a measuring element. It
is used in dust-free, unpolluted, non-aggressive air.
TECHNISCHE DATEN
Power supply:
Load resistance:
Power consumption:
Sensor:
Setting range:
Operating difference:
Output:
Deviation, humidity:
Ambient temperature:
Long-term stability:
Enclosure:
Enclosure dimensions:
Installation:
Protection class:
Protection type:
Electrical connection:
Standards:
Optional:
FUNCTION
Humidifying/heating:
Dehumidifying/cooling:
HYGRASREG
®
RHT - 30 – Room hygrostats and humidity and temperature sensors (± 3 %)
Type ⁄ WG02
Setting Range
Humidity
RHT - 30
R H T- 3 0 W
5...95 % r. H.
R H T- 3 0 W D I S P L AY
5...95 % r. H. +5...+45 °C
RHT - 30 - U
R H T- 3 0 W U
5...95 % r. H. +5...+45 °C
24 V AC (± 20 %), 15...36 V DC
R
> 5 kOhm
L
< 1,5 VA ⁄ 24 V DC, < 3,5 VA ⁄ 24 V AC
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
5...95 % r.H. (Humidity)
+5...+ 45 °C (Temperature)
(switch steps 1 and 2 are separately adjustable)
Mode 1: both switch steps are freely adjustable (rel. humidity)
Mode 2: 5 % between both switch steps (rel. humidity)
Mode 3: both switch steps freely adjustable (temperature)
Mode 4: switch step 1 (temperature), switch step 2 (rel. humidity)
(adjustable via DiP switches)
potential-free changeover contacts (2 x changeover contact 24 V, 1A ohmic load, separately adjustable, 1x 0 - 10 V)
± 3 % r. H. (20...80 %); at + 20 °C, otherwise ± 5 % r. H.
± 0,2 K at +25 °C
storage –35...+85 °C; operation – 30...+70 °C, non-precipitating
± 1 % per year
plastic, material ABS, colour pure white (similar to RAL 9010)
98 x 98 x 35 mm (Baldur 2)
wall mounting or on in-wall flush box, Ø 55 mm, base with 4-hole for mounting on vertically or horizontally installed
in-wall flush boxes for cable entry from the back, with predetermined breaking point for on - wall cable entry from
top ⁄ bottom in case of plain on - wall installation
III (according to EN 60 730)
IP 30 (according to EN 60 529)
0.14 - 1.5 mm
2
, via terminal screws
CE conformity, EMC directive 2014 ⁄ 30 ⁄ EU
two-line display with illumination, cutout approx. 36 x15 mm (W x H),
for displaying ACTUAL humidity and/or ACTUAL temperature respectively for setpoint adjustment
1st step: wire contacts 11 - 12.
If actual humidity falls more than 3 % r.H. / 1 K (hysteresis) below switching threshold S1,
the changeover contact switches to 11 - 12.
2. step: wire contacts 21 - 22.
If actual humidity falls more than 3 % r.H. / 1 K (hysteresis) below switching threshold S2,
the changeover contact switches to 21 - 22.
Terminal 2: output relative humidity / temperature
1st step: wire contacts 11 - 13.
When actual humidity exceeds switching threshold S1, the changeover contact switches to 11 - 13.
2. step: wire contacts 21 - 23.
When actual humidity exceeds switching threshold S 2, the changeover contact switches to 21 - 23.
Terminal 2: output relative humidity / temperatur
Output
Temperature
+5...+45 °C
2 x Changeover contact,
1x 0 -10 V
2 x Changeover contact,
1x 0 -10 V
2 x Changeover contact,
1x 0 -10 V
®
RHT-30 with one continuous and two switching outputs, adjustable switching
Steps
two-step
two-step
two-step
Rev. 2017 - V20 GB
Display
Item No.
External setting
1202- 4077- 1011-200
1202- 4077- 1211-200
Internal setting
1202- 4077- 1021-200

Publicité