The CI-305 has 7 DIP switches under the cover.
Time Delay: Switches 1, 2, 3
The sensor will hold the lights ON as long as occupancy is detected. The time delay countdown starts when
no motion is detected. After no motion is detected for the length of the time delay, the sensor will turn the
lights OFF.
Walk-Through Switch 4
Walk-through mode turns the lights OFF three minutes after the area is initially occupied, if no motion is
detected after the first
30 seconds. If motion continues beyond the first 30 seconds, the selected time delay applies.
PIR Sensitivity: Switch 5
• Minimum forces a reduced detection range for the PIR.
• Maximum forces the sensitivity to the maximum coverage area. This setting is constantly updated.
Service: Switch 6
To override all sensor functions, set DIP switch 6 to the ON position. The red LED will come on and stay on
for the duration of the override. This bypasses the occupancy control functions of the sensor, but still allows
the lights to be manually controlled with a light switch, if one is installed.
On Mode: Switch 7
The Manual ON function is facilitated by installing a momentary switch such as a Wattstopper LVS-1
Momentary Toggle Switch, or RS2-3 Low Voltage Momentary Switch. This switch connects to the sensor's
Manual (Man.) Switch and +24V terminals as shown in the wiring diagram. Each time the switch is pressed,
the load changes state. The sensor's operation as related to the manually operated switch is determined by
the setting for DIP switch 7.
Manual On: In this mode, the switch is required to turn on the load. The sensor is then used to keep the load
on, based on occupant activity. After the time delay ends, if there is no movement detected within the 30
second re-trigger period the manual switch must be used to turn ON the load.
Automatic On: This mode uses occupancy as well as switch activation to turn the load ON. A manual switch provides the following
additional functionality:
1. The load can be turned ON by manual switch activation and it stays on as long as occupancy is detected. The sensor time delay
operates as programmed. When the load turns OFF due to lack of occupancy detection, the load can be turned ON again by
occupancy detection or switch activation.
2. Activating the manual switch while the load is ON turns the load OFF.
• When the load is turned OFF manually, as long as the sensor continues to detect occupancy the load stays OFF. For the
selected time delay, the lights stay off and the sensor reverts to the automatic-on mode.
• When the load is turned OFF manually, pressing the switch again turns the load ON and the sensor reverts to the automatic-on
mode.
• Once the sensor returns to automatic-on mode, either the switch or occupancy detection can turn the load ON.
The occupancy sensor has a built in overload protection function that will automatically turn off the control output when the load current
exceeds 200mA. The sensor LED will then blink rapidly (~ 10Hz) to provide a visual indication of an overload condition. When the load
current is corrected or returns to normal, the control output will turn back on.
Lights do not turn ON with occupancy, and the following condition exists:
Red LED does not flash:
1. Check that the circuit breaker has been turned back on.
2. Check all sensor and power pack wire connections.
3. Check for 24V input to the sensor.
• f 24V is present, replace the sensor.
• If 24V is not present, check that high voltage is present to power pack.
• If it is, replace power pack.
4. Make sure that PIR Sensitivity is set to minimum (DIP switch #5 set to on).
5. If it still does not flash, call 800.879.8585 for Technical Support.
DIP SWITCH SETTING
OVERLOAD PROTECTION
TROUBLESHOOTING
4
DIP Switch Setting Chart
Switch#
Time Delay
1 2 3
Test Mode/20 min
30 seconds
5 minutes
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
Walk-Through
4
Enabled
Disabled
PIR Sensitivity
5
Minimum
Maximum
Service
6
Service
Normal
On Mode
7
Manual On
Auto On
= Factory Setting
= ON
= OFF