Unit with inner panel – KWL EC 45-160
6 .3

Fault causes

Fault
Causes
EC fan not turning
– Mains voltage 230 V failure
– Control voltage 12 V DC failure
– Operating mode Supply air active
– Connection plug not connected or
– Ventilation level 0 activated
– Impeller is blocked
– Motor is defective
– Controller is defective
Vibrations
– Contamination of impeller
– Bearing damage
Abnormal noises
– Grinding impeller
– Bearing damage
– Mechanical damage
Reduced
– Filter and/or fan protection grille is
performance
– Inner panel is closed
– Low ventilation level selected
– Bearing damage
– Heat accumulator is contaminated
6 .4

Standstill and disposal

m
Danger to life due to electric shock!
When dismantling, live parts can be exposed, which can result in electric shock if touched .
Before dismantling, isolate the fan from the mains power supply and protect against being switching on
again!
Parts and components of the fan, whose service life has expired, e.g. due to wear and tear, corrosion, mechanical
load, fatigue and/or other effects that cannot be directly discerned, must be disposed of expertly and properly after
disassembly in accordance with the national and international laws and regulations. The same also applies to auxiliary
materials in use. Such as oils and greases or other substances.
The intended and unintended further use of worn parts, e.g. impellers, rolling bearings, filters, etc. can result in danger
to persons, the environment as well as machines and systems. The corresponding operator guidelines applicable on-
site must be observed and used.
cable break
contaminated
10
Solution
Check mains voltage
Check connection according to wiring diagram
Replace switching power supply
Change operating mode
(please note installation and operating instructions
for controller)
Check connection plug and check connection
cable for breakage, if necessary
Change operating level; note external contact
Clear blockage, clean; contact Helios customer
service team, if necessary
Contact Helios customer service team
Check connection according to wiring diagram
Contact Helios customer service team
Clean impeller
Replace EC fan
Contact Helios customer service team
Clean impeller, replace EC fan, if necessary
Contact Helios customer service team
Replace EC fan
Contact Helios customer service team
Replace defective components
Contact Helios customer service team
Check filter and fan protection grille for contami-
nation and replace filter, if necessary, or clean fan
protection grille
Open inner panel
Increase ventilation level
Replace EC fan
Contact Helios customer service team
Clean heat accumulator