Unit installation

7.2 INSTALLATION SPACE

D
C
> 500 + h2/2
N O T E
Side view. All measurements are in mm.
7.3 INSTALLATION
7.3.1 Installation with walls in two directions
If the units installed are adjacent to high buildings, without walls
in two directions, a space of 300 mm is required at the rear side
of the unit.
> 300
W
W
> 10
> 200
N O T E
All measurements are in mm.
Top view. The arrow ▼ indicates the front of the unit.
W: No limit for side wall height.
7.3.2 Installation with walls in three directions
Single Installation
> 300 + h1/2
> 10
W
> 500 + h2/2
Rear to rear installation 1
> 500 + h2/2
> 10
> 900
W
> 20
> 20
> 500 + h2/2
18
PMML0294A_rev.2_02-2014.indb 18
A
B
765
> 300 + h1/2
> 300
> 500 + h2/2
> 400
> 400
Installation in the same direction
> 300 + h1/2
> 10
> 500
W
> 20
> 20
> 500 + h2/2
Rear to rear installation 2
> 200
> 500
W
>400
>400
> 500 + h2/2
PMML0294A rev.2 - 07/2014
Calculate the service space required during the installation of the
unit, based on the following:
If there are no walls in front of or behind the unit, a space of
500 mm is necessary in front -A- and 300 mm behind -B-.
If the front wall is higher than 1500 mm, a space of (500 +
h2/2) mm is required at the front -A-.
If the rear wall is higher than 500 mm, a space of (300 + h1/2)
mm is required at the back -B-.
If a wall -D- is installed in front of the unit, a ventilation hole
-C- should be made in the wall.
When the space over the unit is less than 1500 mm, or the
space around the unit is closed, a duct is required to prevent
short-circuits between the inlet air and the discharge air.
If there are any obstacles in the space over the unit, the four
sides of the unit should be left open.
N O T E
All measurements are in mm.
Top view. The arrow ▼ indicates the front of the unit.
W: No limit for side wall height.
> 300
7.3.3 Installation with walls in four directions
Single installation
W
> 200
> 800
Rear to rear installation 1
> 200
W
> 800
> 200
> 200
N O T E
All measurements are in mm.
Top view. The arrow ▼ indicates the front of the unit.
W: No limit for side wall height.
Installation in the same direction
> 200
> 300 + h1/2
W
> 200
W
> 800
> 500 + h2/2
> 200
> 200
Rear to rear installation 2
> 500 + h2/2
> 200
> 200
> 1600
W
W
> 800
> 800
> 500 + h2/2
> 400
> 400
> 300 + h1/2
> 200
> 900
W
> 800
> 500 + h2/2
> 500 + h2/2
> 200
> 900
W
> 800
> 500 + h2/2