• Locate a stud within the wall to attach the mounting bracket and
junction box. For concrete or masonry walls, install appropriate
anchors.
• Verify that the stud or anchor and surrounding materials can
• Verify local code with respect to installation height:
• Installation height is regulated by NEC®, however this can
• Junction box should be installed prior to mounting the
VersiCharge to the wall.
• Wire junction box using appropriate wire.
• Attach the Mounting Bracket, using the cutout to line up with the
junction box, to the wall using the two screws.
• Route conductors, with proper strain relief, into the VersiCharge
from the fed-from-behind conductor opening.
• Pull 12 - 18 inches of slack through the conductor opening.
• Mount the VersiCharge to the Mounting Bracket
© 2012 Siemens Industry, Inc.
handle the 20+ lbs load of the VersiCharge.
vary based on local jurisdiction.
• NEC® 2011specifies:
• Indoor (NEC® Article 625.29B) = installation 18 - 48
inches above ground level.
• Outdoor (NEC® Article 625.30B) = installation 24 – 48
inches above ground level.
- 21 -
Document Number: 813540