another.
• We recommend switching a maximum of 3 motion de-
tectors parallel.
• Follow the technical information of the manufacturer.
Button activation ( Page 5 l 3 )
• The motion sensor can be „remotely controlled" (ma-
nuel override) by means of a brief power interruption
of approx. 1 second.
• Connect the power supply (Phase L) to the motion sen-
sor by means of one or several buttons with opening
contact.
• Press the button (with opening contact) and thus brief-
ly interrupt the power supply to the motion sensor.
• After return of power, the motion sensor activates
again.
• The connected lamp is switched on for the duration of
the duty cycle set on the motion sensor.
Parallel circuit with universal switch (off-switch)
( Page 5 l 4 )
• Connect the motion sensor parallel to a universal
switch in order to be able to switch lamps to conti-
nuous illumination.
• Independent of the set duty cycle, the lamp is swit-
ched to continuous illumination as soon as the univer-
sal switch is switched on.
See wiring diagram
Expansion of function by combination with series switch
( Page 6 l 5 )
See wiring diagram
Expansion of function by combination with blind-control
switch ( Page 6 l 6 )
See wiring diagram
Mechanical setting of the detection range
( Page 7 l 7 )
Due to local variations, it may be necessary to vary the
detection range of the motion sensor.
The detection range can be fine tuned by means of hori-
zontal and vertical turning of the sensor head.
15°
35°
Horizontal turning of
the sensor head ap-
prox. +/– 35° (see il-
lustration)
Vertical tilting move-
ment of the sensor
head approx. +/– 15°
(see illustration)
Notes