Final Tests; Periodic Maintenance - SORHEA BIRIS II 50 Notice D'installation

Masquer les pouces Voir aussi pour BIRIS II 50:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SORHEA
7

FINAL TESTS

After installation, verify correct operation with a complete test.
Mode "AND":
 Check interruption of a single cell of two cells: no triggering.
 Check interruption of the two cells: intrusion alarm.
Prolonged interruption of the 2 cells for a period of time longer than 1 min.: disqualification
alarm.
Mode "OR": (BIRIS II 100 & 200 only)
 Check interruption of the top cell: intrusion alarm.
 Check interruption of the bottom cell: intrusion alarm.
Prolonged interruption of one of the 2 cells for a period of time longer than 1 min.:
disqualification alarm.
Mode "AND/OR": (BIRIS II 100 & 200 only)
 Check interruption of one of the two cells for a period of time less than 1.5s.: no triggering
 Check interruption of the two cells: intrusion alarm.
 Check interruption of the top cell for longer than 1.5s: intrusion alarm.
 Check interruption of the bottom cell for longer than 1.5s: intrusion alarm.
 Prolonged interruption of the two cells for a period of time longer than 1 min.: disqualification
alarm.
 Prolonged interruption of the bottom cell for a period of time longer than 1 min.: disqualification
alarm.
8

PERIODIC MAINTENANCE

To ensure proper performance over time, minimum maintenance should be performed:
 Clean the infrared cove of each module at least once a year, (or more often depending on
exposure to foreign elements and grime).
 Repeat the final tests (once per year).
- 31 -
BIRIS II 50/100/200

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Biris ii 100Biris ii 200

Table des Matières