Unit Installation; Initial Check - Hitachi RPF-1.0FSNE Manuel D'installation

Masquer les pouces Voir aussi pour RPF-1.0FSNE:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 23
2
UNITS INSTALLATION
2
2. UNITS INSTALLATION
WARNING:
Check to ensure that the accessories are packed with
-
the indoor unit.
Do not install the indoor units outdoors. If installed
-
outdoors, an electric hazard or electric leakage will
occur.
Consider the air distribution from each indoor unit to
-
the space of the room, and select a suitable location
so that uniform air temperature in the room can be
obtained. It is recommended that the indoor units be
installed 2.3 to 3 meters from the floor level. If the unit
is installed higher than 3 meters, it is also
recommended that a fan be utilised to obtain uniform
air temperature in the room.
Avoid obstacles which may hamper the air intake or
-
the air discharge flow.
Pay attention to the following points when the indoor
-
units are installed in a hospital or other places where
there are electronic waves from medical equipment,
etc.
Do not install the indoor units where electromagnetic
-
wave is directly radiated to the electrical box, remote
control cable or remote control switch.
Prepare a steel box and install the remote control
-
switch in it. Prepare a steel conduit tube and wire the
remote control cable in it. Then connect the ground
wire with the box and tube.
Mount suspension bolts using M10 (W3/8) as size, as
-
shown below:
For Concrete Slab
150~160mm
I-Beam
Steel
Suspension Bolts
Anchor Bolt
(W3/8 or M10)

2.1. UNIT INSTALLATION

2.1.1. FACTORY-SUPPLIED ACCESSORIES
Accessory
Adjustment
Bolt for
Installation
Ring Cores

2.1.2. INITIAL CHECK

Install the indoor unit with a proper clearance around it for
operation and maintenance as shown in Service Access
panel.
RPF
Wall
More Than 300
Wooden Bar
(60 mm to 90 mm Square)
Nuts
Concrete
Square
washers
Wooden Beam
Sling Bolt
(W3/8 or M10)
Quantity
Purpose
For Adjusting the
4
Flat Level of the
Unit
2
Wall
More Than 300
Do not put any foreign material into the indoor unit
-
and check to ensure that none exist in the indoor unit
before the installation and test running. Otherwise a
fire or failure, etc., may occur.
Install a noise filter when the power supply emits
-
harmful noises..
This unit is exclusive non electrical heater type indoor
-
unit. It is prohibited to install a electrical heater in the
field.
CAUTION:
Do not install the indoor units in a flammable
-
environment to avoid a fire or an explosion.
Check to ensure that the ceiling slab is strong
-
enough. If not strong enough, the indoor unit may fall
down on you.
Do not install the indoor units, outdoor unit, remote
-
control switch and cable within approximately 3
meters of strong electromagnetic wave radiators such
as medical equipment.
Do not install the indoor units in a machinery shop or
-
kitchen where vapor from oil or mist flows to the
indoor units. The oil will deposit on the heat
exchanger, thereby reducing the indoor unit
performance, and may deform. In the worst case, the
oil damages the plastic parts of the indoor unit.
To avoid any corrosive action to the heat exchangers,
-
do not install the indoor units in an acid or alkaline
environment.
When lifting or moving the indoor unit, use
-
appropriate slings to avoid damage and be careful not
to damage the insulation material on units surface.
RPFI
Upward Air Outlet
Short Flexible
Duct
Service Space for
Electrical Box
More Than 240
Provide a space so that air can flow smoothly
Front Air Outlet
Service Space for
Electrical Box
More Than 240
Ceiling
Piping Space
More Than 240
Ceiling
Piping Space
More Than 240

Publicité

Table des Matières
loading

Table des Matières