To check the actual value of the
BW
COMPRESSOR TIMERS
C22 GRD : 000s AR : 000s
compressor timers (second screen).
C31 GRD : 000s AR : 000s
C32 GRD : 000s AR : 000s
Safeties menu
The "safeties" menu provides useful information for trouble shooting
purposes. The following screens contain basic information.
To consult which unit safety caused
BX
UNIT SAFETY
0C9 : INL E SENSOR ERR
the shutdown.
To consult which module 1 safety
BX
MODULE 1 SAFETY
1CA : OUT E SENSOR ERR
caused the shutdown.
To consult which module 2 safety
BX
MODULE 2 SAFETY
2CA : OUT E SENSOR ERR
caused the shutdown.
To consult which module 3 safety
BX
MODULE 3 SAFETY
3CA : OUT E SENSOR ERR
caused the shutdown.
Along with the basic information, more detailed information screens
can be consulted while the safety menu is active. Press the q key.
Screens similar to the following will appear.
To check the time and control mode
BC
UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
at the moment of the unit shutdown.
00h00 - 12/01/2001
MANUAL MODE
To check which were the common
BC
UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
evaporator and condenser inlet water
INL.E : 12.0°C STEP:
temperature.
INL.C : 30.0°C 0
To check which were the evaporator
BC
UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
outlet
OUTE1 : 07.0°C OUTE3 :
modules at the moment of shutdown.
OUTE2 : 07.0°C 07.0°C
To check which was the status of the
BC
UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
compressors at the moment of
C11 : ON
C21 :
shutdown (first screen).
C12 : ON
ON
To check which was the status of the
BC
UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
compressors at the moment of
C22 : ON
shutdown (second screen).
To check which were the total
BC
UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
amount of running hours of the com-
RH11 : 00000h RH21:
pressors at the moment of shutdown
RH12 : 00000h 00000h
(first screen).
To check which were the total
BC
UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
amount of running hours of the com-
RH22 : 00000h
pressors at the moment of shutdown
(second screen).
History menu
The "history" menu contains all the information concerning the latest
shutdowns. The structure of those menus is identical to the structure
of the safeties menu. Whenever a failure is solved and the operator
performs a reset, the concerning data from the safeties menu is
copied into the history menu. Warnings are also recorded.
Additionally the number of safeties that already occurred, can be
consulted on the first line of the history screens.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
water
temperature
of
all
Info menu
To consult time and date information.
BX
TIME INFORMATION
TIME : 00h00
DATE : 00/01/2001
To consult additional information
BC
UNIT INFORMATION
UNITTYPE : WW-HP-32
about the unit such as the unit type,
MANUFACT. NR.: 0000000
the refrigerant used and the manu-
REFRIGERANT : R134a
facturing number.
To consult information about the con-
BC
UNIT INFORMATION
SW : V1.0M6 (01/11/01)
troller's software version.
SW CODE : FLDKNMCH0A
To consult information about the
BW
PCB INFORMATION
BOOT : V2.02-02/08/00
PCB.
BIOS : V2.32-31/07/01
Input/output menu
The "input/output" menu gives the status of all the digital inputs and
the relay outputs of the unit.
To
BX
DIGITAL INPUTS
M1 SAFETY OK
safeties are active.
M2 SAFETY OK
M3 SAFETY NOK
To check the reverse phase protector
BC
DIGITAL INPUTS
FLOWSWITCH : FLOW OK
and if there's any waterflow to the
REV.PHASE PR. : OK
evaporator.
To check the status of the change-
BC
CHANG. DIG. INPUTS
DI1 DUAL SETP : SETP.1
able digital inputs.
DI2 REM. ON/OFF : OFF
DI3 REM. C/H : COOL
To check the status of the compres-
BC
RELAY OUTPUTS
C11 : ON
C12 : ON
sor relay outputs.
C21 : ON
C22 : ON
C31 : ON
C32 : OFF
To check the status of the modules
BC
RELAY OUTPUTS
LPBYPASS1 : CLOSED
low pressure bypass.
LPBYPASS2 : CLOSED
LPBYPASS3 : OPEN
To check the status of the alarm
BC
RELAY OUTPUTS
GEN. ALARM : CLOSED
voltage free contact and the pump/
PUMP/GEN OPER : CLOSED
general operation contact.
To check the status of the change-
BW
CHANG. REL OUTPUTS
DO1 REV.VALVE(C/H) : O
able relay output.
User password menu
To change the user password.
B
CHANGE PASSWORD
NEW PASSWORD : 0000
CONFIRM : 0000
Cooling/heating menu
To select cooling or heating mode.
B
COOLING/HEATING
MODE : COOLING (EVAP)
check
whether
any
module
Operation manual