Description Of The Valve; Intended Use - HEROSE 4182 Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 49
3.2
Transportation
Transport the valve in the packaging supplied.
The valve is delivered ready to operate with lateral connections protected by cover caps.
Protect the valve against shocks, impacts, vibrations and dirt.
Adhere to a transport temperature range of -20 °C to +65 °C.
3.3
Storage
Store the valve in a clean and dry place.
Make use of a desiccant or heating in damp storerooms to prevent the formation of
condensation.
Adhere to a storage temperature range of -20 °C to +65 °C.
4

Description of the valve

Refer to the respective catalogue page for further detailed information.
4.1
Structure
Design
Pressure control valve without auxiliary energy.
Component
Body
4.2
Marking
The valves are provided with an individual marking for identification.
Symbol
DN
PN.....
-.....°C
01/18
12345
01234567
0045
e.g. CF8 / 1.4308
4.3

Intended use

The HEROSE combined pressure regulator is for the automatic regulation of pressure in stationary tanks
used for liquefied cryogenic technical gases. Without additional auxiliary energy, the combined pressure
regulator aims to maintain a predefined set operating pressure despite the operation of the tank and
temperature influences in the tank.
In addition to the pressure build-up and the pressure relief/overflow functions, the combined pressure
regulator has a safety function that protects the pipeline and its components on the inlet side.
4.3.1
Pressure build-up function
If the tank pressure falls below the set operating pressure, the combined pressure regulator opens in
order to restore the set operating pressure.
Flow direction AB
4.3.2
Pressure relief / overflow function
If the tank pressure exceeds the set operating pressure by 0.5 bar, the overflow function of the combined
pressure regulator trips in order to restore the set operating pressure.
Flow direction BC
18
Operating instructions
Design
Straight flow type, input A – output B,
output C parallel, central axis A-B
Explanation
Nominal size
Rated working pressure (max. permissible operating
pressure)
+.....°C
Temperature
Manufacturer's mark "HEROSE"
Year of construction MM/YY
Type
Serial no.
CE-mark, ID of notified body
Material
Phone +49 4531 509-0

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

4186

Table des Matières