can cause burns! Do not carry the
meter by the cables.
The maximum heating water tem-
perature at the flow sensor may not
exceed 105ºC or 130°C. For heating
systems with a lack of temperature
mixing resp. with temperature stra-
tification a straight pipeline of min.
10xDN has to be provided upstream
of the meter. It is important to ensure
adequate system pressure to avoid
cavitation. To mount the heat com-
puter of the C5-ISF in combi version
on the wall, the supplied mounting
adapter has to be used.
With heating water temperatu-
res with 90°C and more as soon
as combined heat and coo-
ling measuring or only cooling
measuring the calculator have to
mount on the wall for protection
of external condensation. The
supplied mounting adapter has to
be used. Glycol-compatible meters
may not be used for billing purposes
in commercial traffic. In the case of
refrigeration and combined heat /
cold metering devices, the cash re-
gisters are not calibrated and may
not be used for billing purposes in
commercial transactions. For this
purpose, devices with a separate
type-examination certificate are cur-
rently required.

Mounting flow sensor (DFS)

Mount
ball
downstream of the VMT.
Consider the correct installation
point (supply or return). Normally
valves
up-
and
this is the return pipe (cooler pipe
at heating systems). Please note
the type plate information.
Consider the correct flow direc-
tion. This is indicated by an arrow
on the side of the VMT.
Install horizontally or vertically
only, not tilted, inclined or over-
head. Installation into horizontal
or upstreaming or downstrea-
ming pipelines.
Do not install at highest point of
piping to avoid air inside the flow
sensor.
Consider the dimensions of the
heat meter.
Notes to installation of the ball
valve
Mount
ball
downstream of the meter.
Mount a ball valve with bore
M10x1 for direct sensors in the
supply. This is required for the in-
stallation of the supply sensor
For symmetrical temperature sen-
sor installation, mount an identical
ball valve in the return. This one
is used for mounting the return
sensor.
Mounting heating-/cooling ener-
gy meter
Flush the system thoroughly be-
fore installing the heating-/cooling
energy meter.
Close valves and release pres-
sure.
Dismount the existing flow sensor
or meter blank.
valves
up-
and
23