Note
30 / 120
Siemens
Building Technologies
· Before soldering the valve into the pipework, the flow direction
must be carefully checked
· Make sure that all soldering material, copper grindings etc. are
removed from the pipework
· The valve body must be cooled with a wet cloth during the solder-
ing
· Mount a filter upstream to the valve
· The pipework must be fixed so that the valve connection supports
do not come under any mechanical load. Vibrations can lead to
pipework breaking!
· Evaporator temperature below 0 °C:
the valve body (incl.top/signal converter)and pipework leading
away from the valve must be isolated
· Evaporator temperature above 0 °C:
only the valve body and the pipes leading away from the valve
must be isolated (see picture).
Do not isolate upper part and electronics (overheating)!
Pressure sensor
· Pressure sensor must be mounted upright over the pipework
· Can be mounted directly on the suction pipe
Temperature sensor
·
135°
·
·
The further the sensor is from the evaporator, the more stable the
control (max. 2 m).
It is recommended to increase the setpoint of superheat accordingly.
Superheat - CPS40
System components
Mount as near as possible to the
evaporator outlet (max. distance 2 m / 6.5 ft)
on a straight piece of pipework / immediately
after or on the outside part of an elbow
Fix with a cable tie
Isolate
CE1U3372xx
2018-11-09