Technical Specification - Victron energy Quattro 24/5000/120-100/100-230V Manuel

Masquer les pouces Voir aussi pour Quattro 24/5000/120-100/100-230V:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 59

8. TECHNICAL SPECIFICATION

Quattro
PowerControl / PowerAssist
Integrated Transfer switch
AC inputs (2x)
Maximum feed through current (A)
Minimum PowerAssist current (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25 °C (VA)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
CHARGER
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary AC output
Multi purpose relay
(5)
Protection
(2)
VE.Bus communication port
General purpose comm. port
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 60 Hz and to 240V
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25 °C ambient
5) Programmable relays which can be set for general alarm, DC undervoltage or genset start signal function
AC rating: 230V/4A
DC rating: 4A up to 35VDC, 1A up to 60VDC
26
24/5000/120-100/100
Input voltage range: 187-265 VAC
19 – 33
Output voltage: 230 VAC ± 2%
5000
(3)
4500
4000
10000
94
25
28,8
27,6
26,4
120
(4)
4
For parallel and three phase operation, remote monitoring and system integration
Operating temp.: -20 to +50°C (fan assisted cooling)
Material & Colour: aluminium (blue RAL 5012)
Yes
Yes
Input frequency: 45 – 55 Hz
AC-in-1: 100A
AC-in-2: 100A
AC-in-1: 11A
AC-in-2: 11A
Frequency
yes
Max load: 50A Switches off when in inverter mode
Yes, 3x
a - g
Yes, 2x
Four M8 bolts (2 plus and 2 minus connections)
M6 bolts
31
444 x 328 x 240
EN 60335-1, EN 60335-2-29
EN55014-1, EN 55014-2, EN 61000-3-3
48/5000/70-100/100
Power factor: 1
38 – 66
50 Hz ± 0,1%
:
5000
4500
4000
10000
95
25
57,6
55,2
52,8
70
Humidity (non condensing) : max 95%
Protection: IP 21

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Quattro 48/5000/70-100/100-230v

Table des Matières