12. Technical Specifications

EasySolar-II GX
PowerControl & PowerAssist
Transfer switch
Maximum AC input current
Auxiliary output
Input voltage range
Output
Cont. output power at 25°C (3)
Cont. output power at 40°C / 65°C
Maximum apparent feed-in power
Peak power
Maximum efficiency
Zero load power
Zero load power in AES mode
Zero load power in Search mode
AC Input
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Maximum battery charge current (4)
Battery temperature sensor
Programmable relay (5)
Protection (2)
VE.Bus communication port
General purpose com. port
Model
Maximum output current
Maximum PV power
Maximum PV open circuit voltage
Maximum efficiency
Self-consumption
Charge voltage 'absorption', default
Charge voltage 'float', default setting
Protection (2)
Interfaces
Remote on-off
Operating temp. range
Humidity (non-condensing):
Material & Colour
Protection category
Battery-connection
PV connection
230 V AC-connection
Weight
Dimensions (hxwxd)
Safety
Emission / Immunity
Anti-islanding
1) Can be adjusted to 60 Hz
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 VAC on inverter output
g) input voltage ripple too high
Output voltage: 230 VAC ± 2%
Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz
For parallel and three phase operation, remote monitoring and system integration
SMARTSOLAR MPPT 250/70-Tr
SmartSolar MPPT 250/70-Tr
BMS-Can port (VE.Can not supported), USB, Ethernet, VE.Direct, Wi-Fi
-40 to +65°C (fan assisted cooling)
Screw terminals 13 mm
EN-IEC 60335-1, EN-IEC 60335-2-29
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
3) Non-linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function.
AC rating: 230V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC
INVERTER/CHARGER
yes
32A
32A
32A
INVERTER
38 – 66V
Frequency: 50 Hz ± 0,1% (1)
3000VA / 2400W
2200W / 1700W
2500VA
5500W
95%
11W
7 W
2W
CHARGER
57,6V
55,2V
52,8V
35A
Yes
Yes
a - g
Yes, 2x
70A
4000W
250V
98%
20mA
57,6V
55,2V
a-e
GENERAL
Yes
max 95%
ENCLOSURE
Steel, blue RAL 5012
IP21
M8 bolts
M6 bolts
(6 AWG)
2
26kg
506 x 275 x 147 mm
STANDARDS
EN 55014-1, EN 55014-2
See our website
17