Victron energy EasySolar-II 48/3000/35-32 230V MPPT 250/70 GX Manuel page 12

Masquer les pouces Voir aussi pour EasySolar-II 48/3000/35-32 230V MPPT 250/70 GX:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 41
8.5.3 Programmable analog/digital input/output ports
The product is equipped with 2 analog/digital input/output ports.
These ports can be used for several purposes. One application is communication with the BMS of a lithium-ion battery.
8.5.4 Voltage sense (connection terminal J, see Appendix A)
For compensating possible cable losses during charging, two sense wires can be connected with which the voltage
directly on the battery or on the positive and negative distribution points can be measured. Use wire with a cross-section
of 0,75mm².
During battery charging, the inverter/charger will compensate the voltage drop over the DC cables up to a maximum of 1
Volt (i.e. 1V over the positive connection and 1V over the negative connection). If the voltage drop threatens to become
larger than 1V, the charging current is limited in such a way that the voltage drop remains limited to 1V.
8.5.5 Temperature sensor (connection terminal J, see Appendix A)
For temperature-compensated charging, the temperature sensor (supplied with the inverter/charger) can be connected.
The sensor is isolated and must be fitted to the negative terminal of the battery.
8.5.6 Parallel Connection
It is required to use identical units for three phase and parallel systems. In this case, as only one GX device is allowed
per system, if you wish to parallel and/or three phase with this product, you must find the same model MultiPlus-II to pair.
To assist with finding identical units, consider instead using MultiPlus-II for parallel and three phase systems, and an
external GX device.
Up to six units can be connected in parallel. When connecting this product with MultiPlus-II in a parallel system, the
following requirements must be met:
WARNING
It is essential the negative battery terminal between the units is always connected. A fuse or circuit breaker is
not allowed on the negative.
All units must be connected to the same battery.
A maximum of six units connected in parallel.
The devices must be identical (aside from GX part) and have the same firmware.
The DC connection cables to the devices must be of equal length and cross-section.
If a positive and a negative DC distribution point is used, the cross-section of the connection between the
batteries and the DC distribution point must at least equal the sum of the required cross-sections of the
connections between the distribution point and the units.
Always interconnect the negative battery cables before placing the UTP cables.
Place the units close to each other, but allow at least 10cm for ventilation purposes under, above and beside
the units.
UTP cables must be connected directly from one unit to the other (and to the remote panel). Connection or
splitter boxes are not permitted.
Only one remote control means (panel or switch) can be connected to the system. That means only one GX.
8.5.7 Three-phase operation
The product can also be used in 3-phase wye (Y) configuration. To this end, a connection between the devices is made
by means of standard RJ45 UTP cables (the same as for parallel operation). The system will require subsequent
configuration.
Pre-requisites: see Section Voltage Sense
1.
Note: the product is not suitable for 3-phase delta (Δ) configuration.
2.
When the AS4777.2 grid code has been selected in VEConfigure, only 2 units in parallel per phase are allowed
in a three phase system.
For full details on parallel and three-phase configuration always discuss with your Victron distributor first and please see
this specific manual:
https://www.victronenergy.com/live/ve.bus:manual_parallel_and_three_phase_systems
8.5.8 Connection to the VRM Portal
Connection of the product to VRM requires an internet connection. This can be made via wifi, or preferably a hardwired
ethernet cable to an internet connected router.
The VRM site id is located on a sticker inside the cable connections area of the device.
For more information to set up VRM, refer to the
10
VRM Getting Started Manua

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pmp482307010

Table des Matières