9. Configuration

This section is intended mainly for stand-alone applications
For grid connected Energy Storage Systems (ESS) please see
Settings may only be changed by a suitable qualified installer with the appropriate training, and subject to local
requirements. Please contact Victron for further information or necessary training.
Read the instructions thoroughly before implementing changes.
During setting of the charger, the AC input must be removed.
9.1 Standard settings: ready for use
On delivery, the product is set to standard factory values. In general, these settings are suitable for single-unit operation.
WARNING
Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard factory settings
Setting
Inverter frequency
Input frequency range
Input voltage range
Inverter voltage
Stand-alone / parallel / 3-
phase
AES (Automatic Economy
Switch)
Ground relay
Charger on / off
Battery charge curve
Charging current
Battery type
Automatic equalisation
charging
Absorption voltage
Absorption time
Float voltage
Storage voltage
Repeated absorption time
Absorption repeat interval
Bulk protection
AC input current limit
UPS feature
Dynamic current limiter
WeakAC
BoostFactor
Programmable relay
PowerAssist
9.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in
the software configuration programs.
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50 Hz; 60 Hz
Input frequency range
Input frequency range accepted. The product synchronises within this range with the AC input frequency. The output
frequency is then equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
45 – 65 Hz
180 – 265 VAC
stand-alone
four-stage adaptive with BatterySafe mode
100% of the maximum charging current
Victron Gel Deep Discharge (also suitable for Victron AGM Deep
Discharge)
up to 8 hours (depending on bulk time)
52.8V (not adjustable)
32A (= adjustable current limit for PowerControl and PowerAssist
functions)
alarm function
https://www.victronenergy.com/live/ess:start
Value
50 Hz
230 VAC
off
on
on
Off
57.6V
55.2V
1 hour
7 days
on
on
off
off
2
on
11