Start Up Instructions - ITRON RR16 Mode D'emploi

Masquer les pouces Voir aussi pour RR16:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 34
SAFETY SHUT-OFF VALVE 033
START-UP INSTRUCTIONS
The sequence of start-up the SSV 033 is to be observed!
If the sequence is not considered, the valve disc arm contacts the inside of valve body and the chamfered edge of valve
disc arm (3) can be deformed.
a) Pressure compensation by opening the manipulation valve (self closing) slowly, up to closing pressure of regulator.
b) Unscrew cap (8) of shut-off valve and pull the valve stem (2) by the aid of cap (8), to open the SSV (only possible if pd smaller than
OPSO).
c) Unscrew cap of reset shaft on valve body. Turn the reset shaft (6) in direction of arrow*) until valve disc arm (3) engages into latch
lever.
d) Screw on cap of reset shaft and valve stem.
* For turning reset shaft (6), the maximum torque value is 5 Nm to engage valve disc arm (3) into latch lever.
16
3
6
Stopper
Control line connection
2
8