Notes On Programming - IFM Electronic ecomot200 DW2003 Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

FA-1
MONITOR

Notes on programming

RUN mode
During programming the unit internally remains in the RUN mode! (RUN indicator
visible).
This means that until a new value is acknowledged with the push button
unit carries out its monitoring function on the basis of the previously set parame-
ters and switches the relay and transistor outputs accordingly.
Note:
The monitoring function of the monitor is deactivated by continuously pressing the
button in the RUN mode. The deactivation is effective as long as the push but-
ton is pressed.
Teach function
FH1 Frequency High (maximum value of the frequency range),
FL1
Frequency Low (minimum value of the frequency range) and
SP2 Switch point Output 2.
In addition to the numerical entry the above-mentioned parameters can also be set
by the teach function. In the programming mode this function enables to measure
and display the current input frequency and to assign the selected parameter to it.
To teach the current measured value the same programming steps as for the "nor-
mal" programming are done first.
1. Change from the RUN mode to the parameter range 1 or 2
2. Selection of the requested parameter (FH1, FL1 or SP2)
3. Change to the PRG mode
(PRG indicator visible, parameter abbreviation flashes)
The teaching is started by pressing the
in the PRG mode The current input frequency is displayed and can be changed by
the
or
button on request.
As for the numerical programming the value is stored by pressing the
until the parameter abbreviation no longer flashes and the PRG indicator has dis-
appeared.
Time Out Function
If during programming no pushbutton is pressed for approx. 15 s, this is seen as a
cancellation.
Parameter changes which are not acknowledged with the
jected. The previously set parameter value is restored and remains effective for the
monitoring functions.
page 32
/
buttons simultaneously for approx. 3 s
the
push button
push buttons
push button
button
push button are re-
/

Publicité