The device shall be supplied from an isolating source and protected by an overcur-
rent protection device such that the limited voltage circuit requirements in accor-
dance with UL 508 are met.
If the DC circuit is to be grounded (e.g. due to national regulations), the respective
directives must be adhered to (safe extra-low voltage, circuit electrically separated
from other circuits).
If the unit is AC supplied (DW2003), the low voltage provided for the sensor sup-
ply meets the SELV criteria according to EN 61010, overvoltage category II, soiling
degree 2.
To guarantee safe functioning, signal cables (sensors, transistor outputs, 24 V digi-
tal inputs) and load cables (supply, relay outputs) should be laid separately. If nec-
essary, use a screened cable.
Connection of the sensors (In1)
DC PNP
BN
BK
BU
DC quadronorm
WH
BK
The connection of mechanical switch contacts is not recommended since they tend
to bounce and produce faulty pulses.
The terminals 5/6 can be used to supply the pick-ups with voltage or to trigger the
reset input.
Input reset 1 (external reset)
A pulse (+24 V DC) on terminal 11 resets the relay state latched in case of a fault
if the latching function is active (parameter SO2). If the signal is no longer provid-
ed, the set start-up delay (ST2) starts.
Pressing the pushbuttons continuously does not influence the monitoring function.