Application Parameters - IFM Electronic ecomot200 DW2003 Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

FA-1
MONITOR

Application parameters

Parameter
Description, values, default value
FH1
Frequency High (final value of the frequency range)
Depending on FO1 the analogue minimum and maximum values are indicated.
• Values: 0.0...10,000 Hz or 0...600,000 RPM
For 0...99,999 RPM the increment is 1 RPM,
for values > 99,999 RPM the unit changes from RPM to kRM [kilo Revolutions per
Minute] and the increment is 10 RPM.
• Default value: 1000 (RPM)
Example values: FO1 = 1 (4...20 mA), FH1 = 540 RPM, FL1 = 270 RPM
Result: analogue output 1 provides 4 mA for 270 RPM and 20 mA for 540 RPM.
FL1
Frequency Low (lowest value of the frequency range)
Depending on FO1 the analogue minimum and maximum values are indicated.
The difference between lowest and final value must be at least 5% of the final value!
• Values: 0.0...10,000 Hz or 0...600,000 RPM
For 0...99,999 RPM the increment is 1 RPM,
for values > 99,999 RPM the unit changes from RPM to kRM [kilo Revolutions per
Minute] and the increment is 10 RPM.
• Default value: 0 (RPM)
Example values: FO1 = 5 (20...4 mA), FH1 = 540 RPM, FL1 = 270 RPM
Result: analogue output 1 provides 20 mA for 270 RPM and 4 mA for 540 RPM.
SP2
Switch Point for Out 2 (switch point output 2)
Value at which the output 2 changes its switching state according to switching
function FO2.
• Values: 0,1...10.000 Hz or 1...600.000 RPM (unit depends on DIM)
• Default value: 500 (RPM)
HY2
Hysteresis for Out 2 (hysteresis output 2)
Distance between set and reset point. Prevents a possible chattering of the switching
output. The hysteresis is indicated in % of the switch point SP2.
• Values: 0.0...1000.0 % of the value for SP2
• Default value: 5.0
ST2
Start-Up-Delay for Out 2 (start-up delay for output 2)
To suppress error messages when a plant is started.
When the device is switched on or when the 24 V signal is removed from the reset input,
the respective output is kept in the "good" state independent of the measured value.
• Values: 0.0...1000.0 s
• Default value: 0.0 (inactive start-up delay)
DT2
Delay Time for Out 2 (delay time for output 2)
Enables a delayed switching of the output 2.
In case of a value greater than 0.0 s the output only switches if the current value is
above or below the switch point for more than the time set here.
• Values: 0.0...1000.0 s
• Default value: 0.0 (no delay time)
FT2
Fleeting Time (fleeting function)
If an event occurs, output 2 changes its state for the set time and then switches back
to the initial state.
• Values: 0.0...1000.0 s
• Default value: 0.0 (fleeting time not active)
page 30
Teach function (see page 32)
Teach function (see page 32)
Teach function (see page 32)