Possible Causes - Riello GULLIVER BS1 Manuel D'entretien

Brûleurs gaz à air soufflé
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

BURNER STARTING DIFFICULTIES
FAULTS
The burner will not start
when
the
adjustment
thermostat closes.
The burner runs nor-
mally in the prepurge
and ignition cycle and
locks out after about 3
seconds.
The burner starts with
an ignition delay.
The burner locks out af-
ter the prepurge phase
due to flame-failure.
2146

POSSIBLE CAUSES

Lack of electrical supply.
Lack of gas.
The gas pressure switch does not
close its contact.
The connections in the control box
are wrongly inserted.
The air pressure switch is changed
over to the operational position.
Phase and neutral connection is in-
verted.
The earth connection lacks or is in-
efficient.
The ionization probe is earthed or not
in contact with the flame, or its wiring
to the control box is broken, or there
is a fault on its insulation to the earth.
The ignition electrodes is wrongly
positioned.
Air output is too high.
Valve brake is too close with insuffi-
cient gas output.
The solenoid valves is passing too
little gas.
The solenoid valves are defective.
The ignition arc is irregular or has
failed.
The pipe has not been purged from
the air.
Check presence of voltage in the L1 - N
clamps of the 7 pin plug.
Check the condition of the fuses.
Check that thermostat of max. is not
lock out.
Check the manual cock opening.
Check that the valves charge over to
the opening position and there are not
short circuits.
Adjust them.
Check and connect all the plugs.
Replace the pressure switch.
Invert them.
Make the earth connection efficient.
Check the right position and if neces-
sary set it according to the instructions
of this manual.
Reset the electrical connection.
Replace the faulty connection.
Adjust it according to the instructions
of this manual.
Set the air output according to the in-
structions of this manual.
Adjust it
Check the pressure in the network and/
or adjust the solenoid valve according to
the instructions of this manual.
Change them
Check the right insertion of the con-
nectors.
Check the right position of the electrode
according to the instructions of this man-
ual.
Carry out a complete breathing of the
line of gas-supply.
10 GB
SOLUTION

Publicité

Table des Matières
loading

Table des Matières