Commissioning
Check water flow
Check water flow
The water flow through the boiler can
be checked with two different methods
shown below.
∆T measurement
Check the temperature difference over
the boiler (∆T flow-return) when the
boiler is running on 100% load. The
nominal ∆T is 20K and must be at least
between 15K and 25K for secure boiler
operation. An indication of the actual
flow rate can be found with the follo-
wing calculation (see table below for
nominal data):
q
= (∆T
/ ∆T
actual
nominal
measured
∆p measurement
Check the pressure difference over the
boiler (∆p flow-return) when the boiler
pump is running (burner on is not requi-
red). The nominal ∆p for each boiler
type can be found in the table below,
actual ∆p must be within:
0.35*∆p
≤ ∆P ≤ 1.75*∆p
nom
cation of the actual flow rate can be
found with the following calculation (see
table below for nominal data):
q
= √(∆p
/ ∆p
actual
measured
nominal
Nominal flow
∆p at nom. flow
Nominal flow
∆p at nom. flow
Nominal flow
∆p at nom. flow
Nominal flow
∆p at nom. flow
3
) * q
[m
/h]
nominal
. An indi-
nom
3
) * q
[m
/h]
nominal
Flow rate R3401 - R3405 at ∆T 20K
R3401
3
[m
/h]
[kPa]
Flow rate R3406 - R3410 at ∆T 20K
R3406
3
[m
/h]
[kPa]
Flow rate R3501 - R3505 at ∆T 20K
R3501
3
[m
/h]
[kPa]
Flow rate R3600 - R3605 at ∆T 20K
R3600
3
[m
/h]
[kPa]
R3402
R3403
28.5
31.6
46
53
R3407
R3408
51,6
56,1
58
91
R3502
R3503
26,4
30,8
37
25
R3601
R3602
24,7
27,6
48
56
R3404
R3405
37.0
41.8
36
43
R3409
R3410
64,1
72,1
60
130
R3504
R3505
34,9
39,0
30
35
R3603
R3604
32,2
36,5
38
45
46.8
50
80,1
165
43,0
40
R3605
40,8
45,0
53
60
27