Enregistrement 0X802A (Pdportdatareal) - Siemens SCALANCE X-300 Manuel De Configuration

Commutateurses industrial ethernet
Table des Matières

Publicité

6.4

Enregistrement 0x802A (PDPortDataReal)

Structure
typdef struct{
Word BlockType;
Word BlockLength;
Byte BlockVersionHigh;
Byte BlockVersionLow;
Word Padding;
Word SlotNumber;
Word SubslotNumber;
Byte LengthOwnPortID;
8 Byte OwnPortID;
Byte NumberOfPeers;
Word Padding;
Byte LengthPeerPortID;
8 Byte PeerPortID;
Byte LengthPeerChassisID;
8 Byte PeerChassisID;
Word Padding;
DWord LineDelay;
6 Byte PeerMACAddress;
Word Padding;
Word MAUType;
Word Padding;
DWord DomainBoundary;
DWord MulticastBoundary;
Word LinkState;
Word Padding;
DWord MediaType;};
BlockType
Constante = 0x020F
BlockLength
Constante désigne la longueur de l'enregistrement sans les champs BlockType et
BlockLength.
BlockVersionHigh
Constante =1, désigne la Major Version.
BlockVersionLow
Constante =0, désigne la Minor Version.
SCALANCE X-300 / X-400
Manuel de configuration, 06/2015, C79000-G8977-C187-25
Fonctionnalité PROFINET IO
6.4 Enregistrement 0x802A (PDPortDataReal)
357