4 Faults and flush sequence
4 Faults and flush sequence
5
Séquences "défaut" et "rinçage"
Certain system conditions will release warnings from the control and display system and after a
Certain system conditions will release warnings from the control and display system and after a
specified time it will display fault. In the following, the various warnings and faults will be described with
Certaines conditions du système après un temps spécifique feront apparaitre des messages d'avertissement de défauts. Les divers messages sont
specified time it will display fault. In the following, the various warnings and faults will be described with
their switching sequences.
décrits ci-après.
their switching sequences.
5.1 Pression d'alimentation
4.1 Supply pressure
4.1 Supply pressure
If the supply pressure falls below 1.6 bar, the following warning will be displayed:
Si la pression de l'eau qui alimente le système chute sous 1,6 bar, l'avertissement suivant sera affiché:
If the supply pressure falls below 1.6 bar, the following warning will be displayed:
If the supply pressure is below 1.6 bar for more than 10 seconds, the following fault will be displayed:
If the supply pressure is below 1.6 bar for more than 10 seconds, the following fault will be displayed:
Si la pression d'alimentation reste sous 1,6 bar plus de 10 secondes, le défaut suivant sera affiché:
The motor is switched off and the valves closed. The alarm relay triggered. To acknowledge the alarm,
The motor is switched off and the valves closed. The alarm relay triggered. To acknowledge the alarm,
Danfoss Nessie Humidification
Le moteur électrique est coupé et les électrovannes fermées. Le relais d'alarme est déclenché. Pour confirmer avoir reçu l'information, l'opérateur
the operator must press the OK key once. The alarm persists as long as the supply pressure is below 1.6
the operator must press the OK key once. The alarm persists as long as the supply pressure is below 1.6
doit appuyer une fois sur la touche OK. L'alarme persiste aussi longtemps que la pression reste sous 1,6 bar.
bar.
bar.
5.2 Pression d'humidification
4.2 System pressure
At system pressure below 50 bar, the following warning signal will be shown:
Si la pression de l'humidificateur passe sous 50 bar, l'avertissement suivant apparaitra:
If the system pressure stays below 50 bar for more than 5 minutes, the following fault will be shown:
12
Pression alimentation
Pression alimentation
trop basse!
trop basse!
Défaut
Défaut
Pression alimentation
Pression alimentation
Contrôler alimentation et filtre
Contrôler alimentation et filtre
Réinitialisation: OK
Réinitialisation: OK
Page 16
Page 16
Pression alimentation
basse!
Défaut
521B1002 DKCFN.PS.002.A1.04
Pression alimentation
Contrôler pompe et application