7 INSTALLATION OF WIRED CONTROLLER

The general instructions on wiring in previous chapters should be observed.
The wired controller must be installed indoors and kept away from direct sunlight.
Keep the wired controller away from any ignition source, flammable gas, oil, water vapor, and sulfide gas.
To avoid electromagnetic disturbance, keep the wired controller at a proper distance from electric
appliances, such as lamps.
The circuit of the remote wired controller is a low-voltage circuit. Never connect it with a standard 220-240
V~/380-415 V~ circuit or place it into a same wiring tube with the circuit.
Use a terminal connection block to extend the signal wire if necessary.
Do not use a megger to check insulation of the signal wire upon completion of connection.
7.1 Materials for installation
Verify that the accessory bag contains the following items:
No.
1
Wired controller
2
Wood screw ST 4 × 20
3
Plastic support bar
4
Philips head screw, M 4 × 25
5
Wall plugs
6
Bottom cap of the wired controller

7.2 Dimensions

120 mm
7.3 Wiring
A B X/HA
Y/HB
T1 T2 E1 H1 H2
Hydraulic module
CAUTION
Qty.
Name
1
4
2
2
4
1
18 mm
L1
E
32
Remarks
For mounting on a wall
For mounting on an 86-type box
For mounting on an 86-type box
For mounting on a wall
46 mm
60 mm
HA
HB
H1
H2
E_H
A+
B- Modbus
E
V.1