Intended use also covers installation in accordance
with the IP code.
This appliance can be used by children aged from 8
years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience
and knowledge provided that they have been given
supervision or instruction concerning the use of the
appliance in a safe way and understand the hazards
involved. Children should not play with the appliance.
Cleaning and maintenance should not be made by
children without supervision
Any other use that is not specified in these
instructions, or use beyond that specified in this
document, should be considered as improper use.
Any direct commercial or industrial use is also
deemed to be improper.
CAUTION
Improper use of any kind is prohibited.
Do not rinse the unit.
Do not place any object or equipment on top
of the unit (top plate).
Do not climb, sit or stand on top of the unit.
Regulations to be observed
1)National installation regulations.
2)Statutory
regulations
for
accidents.
3)Statutory regulations for environmental protection.
4)Statutory requirements for pressure equipment:
Pressure Equipment Directive 2014/68/EU.
5)Codes
of
practice
of
associations.
6)Relevant country-specific safety regulations.
7)Applicable regulations and guidelines for operation,
service, maintenance, repair and safety of cooling,
air conditioning and heat pump systems containing
flammable and explosive refrigerant.
Safety instructions for working
on the system
The outdoor unit contains flammable refrigerant R290
(propane C3H8). In case of a leak, the escaping
refrigerant may form a flammable or explosive
atmosphere in the ambient air. A safety zone is
defined in the immediate vicinity of the outdoor unit, in
which special rules apply when work is performed on
the appliance. See section "Safety zone".
Working in the safety zone
DANGER
Risk of explosion: Refrigerant leak may form
a flammable or explosive atmosphere in the
ambient air.
Take the following measures to prevent fire
and explosion in the safety zone:
the
prevention
of
the
relevant
trade
05
Keep ignition sources away, including
naked flames, plug sockets, hot surfaces,
light switches, lamps, electrical devices not
free of ignition sources, mobile devices with
integrated batteries (such as mobile phones
and fitness watches).
Do
not
use
any
combustible gases in the safety zone.
CAUTION
Permissible tools: All tools for working in the
safety
zone
must
explosion-protected in accordance with the
applicable standards and regulations for
refrigerant in safety groups A2L and A3, such
as brushless machines (cordless disposal
containers,
installation
screwdrivers), extraction equipment, vacuum
pumps, conductive hoses, and mechanical
tools of non-sparking material.
CAUTION
The tools must also be suitable for
pressure ranges in use. Tools must be in
perfect maintenance conditions.
The electrical equipment must meet the
requirements for areas at risk of explosion,
zone 2.
Do not use flammable materials such as
sprays or other flammable gases.
Before starting work, discharge static
electricity by touching earthed objects, such
as heating or water pipes.
Do not remove, block or bridge safety
equipment.
Do not make any changes: Do not modify
the outdoor unit, inlet/ outlet lines, electrical
connections/ cables or the surroundings. Do
not remove any components or seals.
Working on the system
Switch off the power supply for the unit (including all
affiliated parts) at a separate fuse or mains isolator.
Check and ensure that the system is no longer live.
CAUTION
In addition to the control circuit there may be
several power circuits.
sprays
or
other
be
designed
and
aids,
and
the
V.1