1. SAFETY

This quick guide contains clearly marked warnings which are intended for your per-
sonal safety and to avoid any unintentional damage to the product or connected ap-
pliances.
Please read these warnings carefully:
This quick guide includes the essential steps for easy
installation and setup of your SmartDrive Compact inverter.
Before commissioning your drive, read the complete
product or downloadable at:
http://inverter.ecc.emea.honeywell.com
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO
CARRY OUT THE ELECTRICAL INSTALLATION
The components of the power unit of the inverter are live when SmartDrive
Compact is connected to mains potential. Coming into contact with this
voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W (T1, T2, T3) and the possible brake resistor
terminals -/+ are live when SmartDrive Compact is connected to mains,
even if the motor is not running.
The control I/O-terminals are isolated from the mains potential. However,
the relay output terminals may have a dangerous control voltage present
even when SmartDrive Compact is disconnected from mains.
The earth leakage current of SmartDrive Compact inverters exceeds
!
3.5mA AC. According to standard EN61800-5-1, a reinforced protective
ground connection must be ensured. See Chapter 7!
If the inverter is used as a part of a machine, the machine manufacturer is
responsible for providing the machine with a main switch (EN 60204-1).
If SmartDrive Compact is disconnected from mains while running the
motor, it remains live if the motor is energized by the process. In this case
the motor functions as a generator feeding energy to the inverter.
After disconnecting the inverter from the mains, wait until the fan stops and
the display segments or status leds on the front panel go out. Wait 5 more
minutes before doing any work on SmartDrive Compact connections.
The motor can start automatically after a fault situation, if autorestart func-
tion has been activated.